Page 188 - SACE Tmax XT - Catalogue
P. 188

7/42             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Remote control














                           Electrical specifications   MOD           MOE and MOE-E               MOE
                                                       XT1 – XT3     XT2 – XT4     XT5           XT6
                                                    [V] 24 DC        24 DC         24 DC         24 DC
                                                    [V] 48…60 DC     48…60 DC      48…60 DC      48…60 DC
                                                    [V] 110…125 AC/DC  110…125 AC/DC  110…125 AC/DC  110…125 AC/DC
                           Rated voltage, Un
                                                    [V] 220…250 AC/DC  220…250 AC/DC  220…250 AC/DC  220…250 AC/DC
                                                    [V] 380…440 AC   380…440 AC    380 AC        380 AC
                                                    [V] 480…525 AC   480…525 AC    -             -
                                                 [% Un] MIN=85% Un;
                           Operating voltage
                                                       MAX=110% Un
                           Power absorbed       [VA - W] ≤ 500       ≤ 300         ≤ 300         ≤ 400
                           on inrush Ps
                           Power absorbed on    [VA - W] ≤ 300       ≤ 150         ≤ 150         ≤ 150
                           continuing PC service
                           Operating frequency     [Hz] 50..60       50..60
                                               CL →OP [s] < 0.1      < 1.5         1.5           3
                           Duration           OP → CL [s] < 0.1      < 0.1         < 0.08        < 0.08
                                              TR → OP [s] < 0.1      < 3           < 3           < 5
                           Mechanical life  N° operations 25000      25000         20000         10000
                           Minimum duration of     [ms] ≥ 150        ≥ 150         ≥ 100         ≥ 100
                           electrical opening and
                           closing command



                           Motor – M
                           Available on SACE Tmax XT7 M only, this motor automatically loads the closing springs of the circuit-
                           breaker. The device automatically reloads the springs of the operating device when they are discharged
                           and energized. In the event of a lack of power, the springs can be manually charged by using a dedicated
                           lever on the operating device. The motor of the XT7 M can be equipped with an S33/M contact which
                           signals the status of the springs that must be ordered separately.

                           Electrical specifications                       Motor Operator XT7 M
                                                                       [V] 24…30 AC/DC
                                                                       [V] 48…60 AC/DC
          —
          Motor operator   Rated voltage, Un                           [V] 100…130 AC/DC
                                                                       [V] 220…250 AC/DC
                                                                       [V] 380…415 AC
                           Operating voltage                         [% Un] MIN=85% Un; MAX=110% Un
                           Power absorbed on inrush Ps              [VA - W] 300
                           Inrush time                                 [ms] 200
                           Power absorbed on continue Pc service    [VA - W] 100
                           Operating frequency                         [Hz] 50..60
                           Charging time                                [s] 8
   183   184   185   186   187   188   189   190   191   192   193