Page 182 - SACE Tmax XT - Catalogue
P. 182

7/36             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Remote control













                           Remote resetting - YR
                           Available on the XT7 M only, the YR reset coil permits the remote resetting of the circuit- breaker after a release
                           has tripped due to an intervention of the protection relay.
                           General characteristics
                           Power supply (Un)            AC                          DC
                               24V                                                 
                               110V                                                
                               220V                                                
                           Operating limits             90%...110% Un
          —
          Remote resetting
                           Opening and closing release test unit - YO/YC Test Unit
                           The opening and closing release test unit helps ensure that the releases are running smoothly, to guar-
                           antee a high level of reliability in controlling circuit-breaker opening. The test unit ensures the service
                           continuity of the opening and closing releases with a rated operating voltage between 24V and 250V
                           (AC and DC), in addition to verifying the functioning of the opening and closing coils electronic circuit.
                           Continuity is checked cyclically at an interval of 30s between tests. The unit has optic signals via LEDs
                           on the front, which provide the following information:
                           POWER ON: correct power supply of the YO/YC Test Unit;
                           OPEN ON: coil switch absent, power supply absent or insufficient, interrupted cables;
                           SHORT ON: coil switch failure, short-circuited cables;
                           OPEN and SHORT FLASHING: faulty coil switch or incorrect supply;
                           OPEN and SHORT OFF: correct operation of the coil switch.
                           Two relays with one change-over area are also available on board the unit, to allow remote signaling of the
                           following events:
                           Test failure - resetting takes place automatically when the alarm stops;
                           Failure of three tests - resetting occurs only by pressing the manual RESET on the unit.

                           Devices characteristics
                           Auxiliary power supply             24...250V AC/DC
                           Specifications of the signaling relays
                           Maximum interrupted current        6A
                           Maximum interrupted voltage        250V AC
   177   178   179   180   181   182   183   184   185   186   187