Page 21 - SACE Tmax XT - Catalogue
P. 21

THE RANGES                                                                        2/3










                                                                                                                       02










 Size  XT1                 XT2                         XT3                            XT4
 Rated uninterrupted current  [A]  160  160            250                          160 / 250
 Poles  [No.]  3, 4         3, 4                       3, 4                           3, 4
 Rated service voltage, Ue  (AC) 50-60Hz  [V]  690  690  690                          690
 Rated insulation voltage, Ui  [V]  800  1000          800                            1000
 Rated impulse withstand voltage, Uimp  [kV]  8  8      8                              8
 Versions  Fixed, Plug-in  (1)  Fixed, Withdrawable, Plug-in  Fixed, Plug-in  Fixed, Withdrawable, Plug-in
 Max supply voltage on  bottom side (F, P, W)  [V]  690  ≤ 480  690                   ≤ 600
 Breaking capacities according to IEC 60947-2  N  S  H  L  V  N  S  H  L  V  N  S  N  S  H  L      V       X
 Rated ultimate short-circuit breaking capacity, Icu
 Icu @ 220-230-240V 50-60Hz (AC)  [kA]  25  40  65  85  100  65  85  100  150  200  50  85  65  85  100  150  200  200
 Icu @ 380V 50-60Hz (AC)  [kA]  18  25  36  50  70  36  50  70  120  150  36  50  36  50  70  120  150    200
 Icu @ 415V 50-60Hz (AC)  [kA]  18  25  36  50  70  36  50  70  120  150  36  50  36  50  70  120  150    200
 Icu @ 440V 50-60Hz (AC)  [kA]  15  25  36  50  65  36  50  65  100  150  25  40  36  50  65  100  150    200
 Icu @ 500V 50-60Hz (AC)  [kA]  8  18  30  36  50  30  36  50  60  70  20  30  30  36  50  60     85      100
 Icu @ 525V 50-60Hz (AC)  [kA]  6  8  22  35  35  20  25  30  36  50  13  20  20  25  45   50     70      100
 Icu @ 690V 50-60Hz (AC)  [kA]  3  4  6  8  10  10  12  15  18  20  5  6  10  12   15      20     50  (2)  100
 Rated service short-circuit breaking capacity, Ics
 Ics @ 220-230-240V 50-60Hz (AC)  [kA]  100%  100%  75% (50)  75%  75%  100%  100%  100%  100%  100%  75%  50%  100%  100%  100%  100%  100%  100%
 Ics @ 380V 50-60Hz (AC)  [kA]  100%  100%  100%  100%  75%  100%  100%  100%  100%  100%  75%  50% (27)  100%  100%  100%  100%  100%  100%
 Ics @ 415V 50-60Hz (AC)  [kA]  100%  100%  100%  75%  50% (37.5)  100%  100%  100%  100%  100%  75%  50% (27)  100%  100%  100%  100%  100%  100%
 Ics @ 440V 50-60Hz (AC)  [kA]  75%  50%  50%  50%  50%  100%  100%  100%  100%  100%  75%  50%  100%  100%  100%  100%  100%  100%
 Ics @ 500V 50-60Hz (AC)  [kA]  100%  50%  50%  50%  50%  100%  100%  100%  100%  100%  75%  50%  100%  100%  100%  100%  100%  100%
 Ics @ 525V 50-60Hz (AC)  [kA]  100%  100%  50%  50%  50%  100%  100%  100%  100%  100%  75%  50%  100%  100%  100%  100%  100%  100%
 Ics @ 690V 50-60Hz (AC)  [kA]  100%  100%  75% (5)  50% (5)  50%  100%  100%  100%  75% (15)  75%  50% (3)  50%  100%  100%  100%  100%  100% (3)  100% (3)
 Rated short-circuit making capacity, Icm
 Icm @ 220-230-240V 50-60Hz (AC)  [kA]  52.5  84  143  187  220  143  187  220  330  440  110  187  143  187  220  330  440  440
 Icm @ 380V 50-60Hz (AC)  [kA]  36  52.5  75.6  110  154  75.6  110  154  264  330  75.6  110  75.6  110  154  264  330  440
 Icm @ 415V 50-60Hz (AC)  [kA]  36  52.5  75.6  110  154  75.6  110  154  264  330  75.6  110  75.6  110  154  264  330  440
 Icm @ 440V 50-60Hz (AC)  [kA]  30  52.5  75.6  110  143  75.6  110  143  220  330  52.5  84  75.6  110  143  220  330  440
 Icm @ 500V 50-60Hz (AC)  [kA]  13.6  36  63  75.6  110  63  75.6  110  132  154  40  63  63  75.6  110  132  187  220
 Icm @ 525V 50-60Hz (AC)  [kA]  9  13.6  46.2  73.5  73.5  40  52.5  63  75.6  110  26  40  40  52.5  94.5  110  154  220
 Icm @ 690V 50-60Hz (AC)  [kA]  4.26  5.88  9  13.6  17  17  24  30  36  40  7.5  9  17  24  30  40  110  220
 Breaking capacities according to NEMA-AB1
 @ 240V 50-60Hz (AC)  [kA]  25  40  65  85  100  65  85  100  150  200  50  85  65  85  100  150  200     200
 @ 480V 50-60Hz (AC)  [kA]  8  18  30  36  65  30  36  65  100  150  25  35  30  36  65   100     150     100
 Utilization Category (IEC 60947-2)  A  A               A                              A
 Icw  [kA]  -                -                          -                              -
 Reference Standard  IEC 60947-2  IEC 60947-2       IEC 60947-2                     IEC 60947-2
 Insulation behaviour                                                               
 Mounted on DIN rail  DIN EN 50022  DIN EN 50022   DIN EN 50022                    DIN EN 50022
 [No. Operations]  25,000  25,000                     25,000                         25,000
 Mechanical life
 [No. Hourly operations]  240  240                     240                            240
 [No. Operations]  8,000   8,000                      8,000                   8,000                  10,000
 Electrical life @ 415 V (AC)
 [No. Hourly operations]  120  120                     120                            120
 (1)  XT1 plug-in In max=125A     (2) In<32A Icu=25kA/Ics=20kA, with magnetic trip unit only and In≤52A/Icu=Ics=5kA
 (3) Ics=100% Icu up to 250 A with EF, ES, Rear and external FC CuAl (2x...) terminal. When any other terminals are used and load >200A Icu=25%