2/6              SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          SACE Tmax XT automatic circuit-breakers for

          alternating current (AC) distribution











          Size                                                                         XT5                                                XT6 (1)                            XT7                                  XT7 M
          Rated uninterrupted current                          [A]                   400 / 630                                          800 / 1000  (6)               800 / 1000 / 1250 / 1600             800 / 1000 / 1250 / 1600
          Poles                                               [No.]                    3. 4                                                3. 4                              3. 4                                 3. 4
          Rated service voltage. Ue  (AC) 50-60Hz              [V]                     690                                                 690                               690                                  690
          Rated insulation voltage. Ui                         [V]                     1000                                               1000                              1000                                  1000
          Rated impulse withstand voltage. Uimp               [kV]                      8                                                   8                                 8                                    8
          Versions                                                            Fixed. Withdrawable. Plug-in  (5)                      Fixed. Withdrawable               Fixed. Withdrawable                   Fixed. Withdrawable
          Max supply voltage on  bottom side (F. P. W)         [V]                     690                                                 690                               690                                  690
          Breaking capacities according to IEC 60947-2               N       S      H       L      V       X                        N       S      H                   S      H       L                    S       H      L
          Rated ultimate short-circuit breaking capacity. Icu
          Icu @ 220-230-240V 50-60Hz (AC)                     [kA]   70     85      100    150     200    200                      70      85      100                85      100    200                  85      100     200
          Icu @ 380V 50-60Hz (AC)                             [kA]   36     50      70     120     200    200                      36      50      70                 50      70      120                 50      70      120
          Icu @ 415V 50-60Hz (AC)                             [kA]   36     50      70     120     200    200                      36      50      70                 50      70      120                 50      70      120
          Icu @ 440V 50-60Hz (AC)                             [kA]   36     50      65     100     180    200                      30      45      50                 50      65      100                 50      65      100
          Icu @ 500V 50-60Hz (AC)                             [kA]   25     30      50      85     150    150                      25      35      50                 45      50      85                  45      50      85
          Icu @ 525V 50-60Hz (AC)                             [kA]   25     30      50      85     100    120                      25      35      50                 45      50      65                  45      50      65
          Icu @ 690V 50-60Hz (AC)                             [kA]   20     25      40      70     80     100                      20      22      25                 30      42      50                  30      42      50
          Rated service short-circuit breaking capacity. Ics
          Ics @ 220-230-240V 50-60Hz (AC)                     [kA]  100%   100%    100%   100%    100%    100%                    100%    100%    100%               100%    100%    100%                100%    100%    100%
          Ics @ 380V 50-60Hz (AC)                             [kA]  100%   100%    100%   100%    100%    100%                    100%    100%    100%               100%    100%    100%                100%    100%    100%
          Ics @ 415V 50-60Hz (AC)                             [kA]  100%   100%    100%   100%    100%    100%                    100%    100%    100%               100%    100%    100%                100%    100%    100%
          Ics @ 440V 50-60Hz (AC)                             [kA]  100%   100%    100%   100%    100%    100%                    100%    100%    100%               100%    100%    100%                100%    100%    100%
          Ics @ 500V 50-60Hz (AC)                             [kA]  100%   100%    100%   100%    100%    100%                    100%    100%    100%               100%    100%    100%                100%    100%    100%
          Ics @ 525V 50-60Hz (AC)                             [kA]  100%   100%    100%   100%    100%    100%                    100%    100%    100%               100%    100%    100%                100%    100%    100%
          Ics @ 690V 50-60Hz (AC)                             [kA]  100%   100%   100% (2)  100% (3)  100% (3)  100%  (3)         100%    100%    100%               100%    100%    100%                100%    100%    100%
          Rated short-circuit making capacity. Icm
          Icm @ 220-230-240V 50-60Hz (AC)                     [kA]  154     187     220    330     440    440                      154     187     220                187     220    440                  187     220     440
          Icm @ 380V 50-60Hz (AC)                             [kA]  75.6    110     154    264     440    440                      75.6    110     154                110     154     264                 110     154     264
          Icm @ 415V 50-60Hz (AC)                             [kA]  75.6    110     154    264     440    440                      75.6    110     154                110     154     264                 110     154     264
          Icm @ 440V 50-60Hz (AC)                             [kA]  75.6    110     143    220     396    440                      63      94.5    110                110     143     220                 110     143     220
          Icm @ 500V 50-60Hz (AC)                             [kA]  52.5    63      110    187     330    330                      52.5    73.5    110                94.5    110     187                 94.5    110     187
          Icm @ 525V 50-60Hz (AC)                             [kA]  52.5    63      110    187     220    264                      52.5    73.5    110                94.5    110     143                 94.5    110     143
          Icm @ 690V 50-60Hz (AC)                             [kA]   40     52.5    84     154     176    220                      40      46.2   52.5                63     88.2     110                 63      88.2    110
          Breaking capacities according to NEMA-AB1
          @ 240V 50-60Hz (AC)                                 [kA]
          @ 480V 50-60Hz (AC)                                 [kA]
          Utilization Category (IEC 60947-2)                                  A (up to 630A). B (up to 500A)  (4)                  A (up to 1000A) - B (800A)  (4)            B                                    B
          Icw (1 sec)                                         [kA]                      6                                                  10                                20                                    20
          Reference Standard                                                        IEC 60947-2                                         IEC 60947-2                       IEC 60947-2                           IEC 60947-2
          Insulation behaviour                                                                                                                                                                                  
          Mounted on DIN rail                                                           -                                                   -                                 -                                    -
                                                      [No. operations]                20,000                                              20,000                            10,000                               20,000
          Mechanical life
                                                 [No. hourly operations]               120                                                 120                               60                                    60
                                                      [No. operations]         7,000 (400A) - 5,000 (630A)                                5,000                             3,000                                 3,000
          Electrical life @ 415 V (AC)
                                                 [No. hourly operations]                60                                                 60                                60                                    60
          (1) Not suitable for IT distribution systems > 440Vac     (2) Ics = 75% In > 500A     (3) Ics = 50% In > 500A     (4) Category B: only when equipped with an  electronic trip unit                                                            (5) Plug-in/Withdrawable: max In 40°C=600A     (6) 1000A only for fixed execution with EF. ES. R and FCCuAl terminals. EF terminals are supplied as standard if no other terminals are ordered