Page 19 - Slimline Fuse Switches
P. 19

PRODUCT OVERVIEW                                                                   19



          —

          Product overview


          Motor operation (MOT)




          SlimLine XR Gold offers an integrated motor for remote and local operation.
          The motor operation unit is 100% integrated and does not increase external                                   02
          dimensions. The front operated ON/OFF buttons are protected by a transparent
          cover with padlocking facility.



          With the new improved Utilization category AC23A, SlimLine XR Gold enables
          up to 8000 operations. This is a perfect solution for load shedding.
          Load shedding is possible with only MOT or with MOT+ ITS2.1.






























                    EFM + MOT New multi plug P

                                   L1
                                   L2
                                   L3
                                   (N)
                                   PE(N)
                    Q1
                                                                          Q1. Switch disconnector Fuse
                                                                          K1: Electronic Fuse Monitor (EFM)
                                                                          V1: Fuses OK
                                                                          V2: Fuse(s) fail(ed)
                                                                          X1: Multiplug terminals
                      M                                                   S1: Close
                            F1 F2 F3
                                                                          S2: Open
                                         K1          X1
                                                     11  NO
                                                     13  NC
                                                     12  EFM Common
                                                     14  Switch position feedback NO (*)
                                                     15  Switch position feedback NO (*)
                                                     16  Field Close
                                                     17  Field Open
                                                     18  Field Common     (*)   Contact follow main contact. Will go to NO at loss
                                                     19  +24V
                                                     20 0V                  OF+24V for indication purposes only.
                                     S1  S2  V1 V2
   14   15   16   17   18   19   20   21   22   23   24