Page 46 - Slimline Fuse Switches
P. 46
46 SLIMLINE XR GOLD SWITCH DISCONNECTOR FUSE
—
Technical data
SlimLine XR Gold–Switch disconnector fuses
—
3-pole
Type XRG00 XRG1 XRG2 XRG3
Rated operational voltage Ue (V) 500 690 500 690 800 500 690 500 690
Rated operational current Ie (A) 160 125 250 250 250 400 400 630 500
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (V) 8000 8000 8000 8000 8000 8000 8000 8000 8000
Fuse protected short circuit making (kArms) 120 100 120 100 100 120 100 120 100
Fuse protected short circuit withstand (kArms) 120 100 120 100 100 120 100 120 100
Rated making and breaking capacity AC23A AC23A AC23A AC23A AC22B AC23A AC23A AC23A AC23A
Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Durability: Total / 8000/ 8000/ 8000/ 8000/ 1600/ 5000/ 5000/ 5000/ 5000/
With current 1000 1000 1000 1000 200 1000 1000 1000 1000
Degree of protection from the front acc.
to IEC / EN 60529 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41 IP41
Type tested according to IEC 60947-3.
Tested with gG fuse.
Valid also for BS fuses.
—
4-pole
Type XRG00 XRG1 XRG2 XRG3
Rated operational voltage Ue (V) 500 500 500 500
Rated operational current Ie (A) 160 250 400 630
Rated insulation voltage Ui (V) 1000 1000 1000 1000
Rated impulse withstand voltage Uimp (V) 8000 8000 8000 8000
Fuse protected short circuit making (kArms) 55 55 55 55
Fuse protected short circuit withstand (kArms) 100 100 100 100
Rated making and breaking capacity AC22B AC22B AC22B AC22B
Rated frequency (Hz) 50/60 50/60 50/60 50/60
Durability: Total / With current 1600/200 1600/200 1000/200 1000/200
Degree of protection from the front acc.
to IEC / EN 60529 IP41 IP41 IP41 IP41
Type tested according to IEC 60947-3.
Tested with gG fuse.
Valid also for BS fuses.