Page 47 - Slimline Fuse Switches
P. 47

TECHNIC AL DATA                                                                    47




          —
          Technical data
          SlimLine XR Gold–Switch disconnector fuses











          —
          2-pole
          Type                                        XRG00             XRG1              XRG2              XRG3
          Rated operational voltage Ue (V)     230      500      230     500      230      500      230      500
          Rated operational current Ie (A)     125      160      250     250      400      315      630      400       04
          Rated insulation voltage Ui (V)     1000     1000     1000     1000    1000     1000     1000      1000
          Rated impulse withstand voltage Uimp (V)  8000  8000  8000    8000     8000     8000     8000     8000
          Fuse protected short circuit making (kArms)  66  66    66       66       66       66       66       66
          Fuse protected short circuit withstand (kArms)  100  100  100  100      100      100      100      100
          Rated making and breaking capacity  DC23B   DC21B    DC23B    DC21B   DC23B    DC21B    DC23B     DC21B
          Durability: Total /                 1600/   1600/    1600/    1600/    1000/   1000/    1000/     1000/
          With current                         200      200      200     200      200      200      200      200
          Degree of protection from the front acc.
          to IEC / EN 60529                    IP41     IP41    IP41     IP41     IP41     IP41    IP41      IP41
          Type tested according to IEC 60947-3.
          Tested with gG fuse.
          Tests run at AC.
          Valid also for BS fuses.



         —
         Power losses in SlimLine XRG
         Size                                                      00             1             2             3
         Rated current                               (A)          160           250           400           630
         Power losses*                              (W)            33            70            100           245
         *The values given include all three phases, but without fuses.




          —
          Type of Fuses for XRG BS versions
          Current                                                 Fuse Type                 Distance between fuse bolts
          63 A                                                         A3                                  72 mm
          100 A                                                        A3                                  72 mm
          160 A                                                  00T Lawson                                72 mm
          250 A                                                        B2                                 110 mm
          400 A                                                        B4                                 112 mm
          630 A                                                   3T Lawson                               112 mm
   42   43   44   45   46   47   48   49   50   51   52