Page 48 - Slimline Fuse Switches
P. 48
48 SLIMLINE XR GOLD SWITCH DISCONNECTOR FUSE
—
Technical data
Electronic Fuse Monitoring (EFM) and Motor operation (MOT)
—
Technical data for XRG EFM
Input voltage limits DC AC
Rated AC voltage Ue 280…880 VAC
DC 110: Rated DC voltage Ue 45 ... 140 VDC
DC 550: Rated DC voltage Ue 135 ... 550 VDC
Power consumption 2 W < 3V A
Functional characteristics
Operating time to ≤ 4 s ≤ 2s
Measuring accuracy ± 5%
Signaling relay output terminals (multiplug)
Normally opened Terminal 11 - 12 Terminal 11 - 12
Normally closed Terminal 12 - 13 Terminal 12 - 13
Rated load, resistive 4 A at 24 VDC Utilization category DC-1 8 A at 24 VDC
Rated load, inductive 2 A at 24 VDC Utilization category DC-13 2 A at 24 VDC
Rated load, resistive 4 A at 240 VAC Utilization category AC-1 8 A at 250 VAC
Rated load, inductive 3 A at 240 VAC Utilization category AC-15 5 A at 250 VAC
Stranded/solied 0,14 - 1,5 Stranded/solied 0,14 - 1,5
Wiring capacity (mm²) Stranded with ferrule, with/without Stranded with ferrule, with/without
plastic sleeve 0,25-0,5/0,25-1,5 plastic sleeve 0,25-0,5/0,25-1,5
Dielectric properties (IEC 60947-1)
Rated impulse withstand voltage (Uimp), basic insulation 2,5 kV/6,0 kV 9,8 kV
All poles connected together/Earth 1,5 kV / 1,89 kV / 1 min 50 Hz 3,5 kV / 1 min 50 Hz
All poles connected together/Auxiliary contacts 1,89 kV / 1 min 50 Hz 3,5 kV / 1 min 50 Hz
Insulation resistance > 1 MΩ, 500 VDC
EMC characteristics
Electrostatic Discharge EN 6100-4-2 Air 8 kV ± 8 kV
Electrostatic Discharge EN 6100-4-2 Contact 4 kV ± 4 kV
Electrostatic Fast Transient EN 6100-4-4 Level 3 Level 3
Surge immunity EN 6100-4-5 Level 2 Level 2
Power frequency magnetic field EN 6100-4-8 Level 5 Level 5
MTBF 1.103.137 hours at 80°C
—
Technical data for Motor operation (MOT)
Technical data MOT XRG MOT
Operational voltage 24 VDC ± 2 Volt
Operational consumption peak value * 1,1 A
Signal duration Min. 0,5 sec. or permanent
Minimum number of operations According to IEC / EN 60947-3
* Recommended power supply 10 A.