Page 48 - Slimline Fuse Switches
P. 48

48               SLIMLINE XR GOLD SWITCH DISCONNECTOR FUSE




          —
          Technical data
          Electronic Fuse Monitoring (EFM) and Motor operation (MOT)






         —
         Technical data for XRG EFM
         Input voltage limits                      DC                             AC
         Rated AC voltage Ue                                                      280…880 VAC
         DC 110: Rated DC voltage Ue               45 ... 140 VDC
         DC 550: Rated DC voltage Ue               135 ... 550 VDC
         Power consumption                         2 W                            < 3V A
         Functional characteristics
         Operating time to                         ≤ 4 s                          ≤ 2s
         Measuring accuracy                        ± 5%
         Signaling relay output terminals (multiplug)
         Normally opened                           Terminal 11 - 12               Terminal 11 - 12
         Normally closed                           Terminal 12 - 13               Terminal 12 - 13
         Rated load, resistive                     4 A at 24 VDC Utilization category DC-1  8 A at 24 VDC
         Rated load, inductive                     2 A at 24 VDC Utilization category DC-13  2 A at 24 VDC
         Rated load, resistive                     4 A at 240 VAC Utilization category AC-1  8 A at 250 VAC
         Rated load, inductive                     3 A at 240 VAC Utilization category AC-15  5 A at 250 VAC
                                                   Stranded/solied 0,14 - 1,5     Stranded/solied 0,14 - 1,5
         Wiring capacity (mm²)                     Stranded with ferrule, with/without   Stranded with ferrule, with/without
                                                   plastic sleeve 0,25-0,5/0,25-1,5  plastic sleeve 0,25-0,5/0,25-1,5
         Dielectric properties (IEC 60947-1)
         Rated impulse withstand voltage (Uimp), basic insulation  2,5 kV/6,0 kV  9,8 kV
         All poles connected together/Earth        1,5 kV / 1,89 kV / 1 min 50 Hz  3,5 kV / 1 min 50 Hz
         All poles connected together/Auxiliary contacts  1,89 kV / 1 min 50 Hz   3,5 kV / 1 min 50 Hz
         Insulation resistance                     > 1 MΩ, 500 VDC
         EMC characteristics
         Electrostatic Discharge EN 6100-4-2 Air   8 kV                           ± 8 kV
         Electrostatic Discharge EN 6100-4-2 Contact  4 kV                        ± 4 kV
         Electrostatic Fast Transient EN 6100-4-4  Level 3                        Level 3
         Surge immunity EN 6100-4-5                Level 2                        Level 2
         Power frequency magnetic field EN 6100-4-8  Level 5                      Level 5
         MTBF                                                                     1.103.137 hours at 80°C





         —
         Technical data for Motor operation (MOT)
         Technical data MOT                        XRG MOT
         Operational voltage                       24 VDC   ± 2 Volt
         Operational consumption peak value *      1,1 A
         Signal duration                           Min. 0,5 sec. or permanent
         Minimum number of operations              According to IEC / EN 60947-3
         * Recommended power supply 10 A.
   43   44   45   46   47   48   49   50   51   52   53