Page 163 - Surge-Protection-E_0.pdf
P. 163
Pluggable SPDs – DIN Rail Mounted
BCO MOD ML2 BD 927 042 927 044 927 045 BCO MOD ML2 BD 12
BCO MOD ML2 BD 24
BCO MOD ML2 BD 48
Protection module with a width of 6 mm for BLITZDUCTORconnect combined arrester with status inidication for protecting one pair of
unearthed balanced interfaces.
79,00 €
927 042 4013364410152 04 02 01 06 14 g
927 044 4013364410169 04 02 01 06 14 g
79,00 €
927 045 4013364410176 04 02 01 06 14 g
79,00 €
Type BCO ... MOD ML2 BD 12 MOD ML2 BD 24 MOD ML2 BD 48
Part No. 927 042 + 927 044 + 927 045 +
SPD class L L L
Nominal voltage (UN) 12 V 24 V 48 V
Max. continuous operating voltage (d.c.) (UC) 15 V 36 V 56 V
Nominal current at 70 °C (IL) 0.75 A 0.75 A 0.75 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1.5 kA 1.5 kA 1.5 kA
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 10 kA 10 kA 1 1‘
Series resistance per line 1 ohm(s) 1 ohm(s) 1 ohm(s) protected
2 2‘
Cut-off frequency line-line (fG) 2.6 MHz 5.8 MHz 3.6 MHz Pluggable SPDs – DIN Rail Mounted
Approvals UL, SIL UL, SIL UL, SIL
BCO MOD ML2 BE HF 927 070 BCO MOD ML2 BE HF 5
Protection module with a width of 6 mm for BLITZDUCTORconnect combined arrester with status inidication for protecting two single lines
of high-frequency transmissions sharing a common reference potential as well as unbalanced interfaces. 927 070 4013364410183 04 02 01 06 14 g
86,00 €
Type BCO ... MOD ML2 BE HF 5
Part No. 927 070 +
SPD class M
Nominal voltage (UN) 5 V
Max. continuous operating voltage (d.c.) (UC) 8.5 V
Nominal current at 70 °C (IL) 0.75 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1.5 kA 1 1‘
C2 Total nominal discharge current (8/20 µs) (In) 10 kA protected
2 2‘
Series resistance per line 1 ohm(s)
Approvals UL, SIL
BCO MOD ML2 BD HF
Protection module with a width of 6 mm for BLITZDUCTORconnect combined arrester with status inidication for protecting one pair of 927 071 BCO MOD ML2 BD HF 5
unearthed high-frequency bus systems as well as balanced interfaces. 927 071 4013364410190 04 02 01 06 14 g
86,00 €
Type BCO ... MOD ML2 BD HF 5
Part No. 927 071 +
SPD class L
Nominal voltage (UN) 5 V
Max. continuous operating voltage (d.c.) (UC) 8.5 V
Nominal current at 70 °C (IL) 0.75 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1.5 kA
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 1 1‘
Series resistance per line 1 ohm(s) protected
2 2‘
Cut-off frequency line-line (fG) 100 MHz
Approvals UL, SIL
927 084 BCO MOD ML2 BD EX 24
BCO MOD ML2 BD EX 24
927 084 4013364410206 04 02 01 06 14 g
84,00 €
Protection module with a width of 6 mm for BLITZDUCTORconnect combined arresters with status indication for protecting one pair of intrin-
sically safe measuring circuits and bus systems, meets FISCO requirements. Insulation strength > 500 V line-ground.
Type BCO ... MOD ML2 BD EX 24
Part No. 927 084 +
SPD class L
Nominal voltage (UN) 24 V
Max. continuous operating voltage (d.c.) (UC) 36 V
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1.5 kA
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 1 1‘
Series resistance per line 1 ohm(s) protected
2 2‘
Cut-off frequency line-line (fG) 3.5 MHz
Approvals SIL, ATEX, IECEx
Valid as of August 1, 2020 You will find detailed product information on our website 159