Pluggable SPDs – DIN Rail Mounted

                         BXT ML4 BC 5 / 24
        920 350   BXT ML4 BC 5
        920 354   BXT ML4 BC 24
                         Space-saving combined lightning current and surge arrester module with RFID LifeCheck for protecting up to four unearthed single lines
        920 350   4013364109131  04 02 01 02   24 g
              206,10 €   sharing a common reference potential.
        920 354   4013364109148  04 02 01 02   24 g
              206,10 €
                          Type BXT ...                      ML4 BC 5                 ML4 BC 24
                          Part No.                          920 350                  920 354
                          SPD class                         M                        M
        1               1´
                          Max. continuous operating voltage (d.c.)  (UC)  6.0 V      33 V
                          Nominal current at 45 °C  (IL)    1.0 A                    0.75 A
        2               2´
                          D1 Total lightning impulse current (10/350 µs)  (Iimp)  10 kA  10 kA
                        protected  3´  C2 Total nominal discharge current (8/20 µs)  (In)  20 kA  20 kA
   Pluggable SPDs –   DIN Rail Mounted  4  4´  Cut-off frequency line-line  (fG)  1.0 MHz  5.7 MHz
                          Series resistance per line
                                                            1.0  ohm(s)
                                                                                     1.8  ohm(s)
        3
                                                            CSA, EAC, ATEX, IECEx,
                                                                                     CSA, EAC, ATEX, IECEx,
                          Approvals
                                                                                     CSA & USA Hazloc, SIL
                                                            CSA & USA Hazloc, SIL
                         BXT ML4 BE C 12 / 24
        920 362   BXT ML4 BE C 12
        920 364   BXT ML4 BE C 24
                         Space-saving combined lightning current and surge arrester module with RFID LifeCheck for protecting two pairs of balanced interfaces with
        920 362   4013364120587  04 02 01 02   24 g
              239,50 €   diode protective circuit at the input, current loops (TTY) and optocoupler inputs.
        920 364   4013364109155  04 02 01 02   25 g
              239,50 €
                          Type BXT ...                      ML4 BE C 12              ML4 BE C 24
                          Part No.                          920 362                  920 364
                          SPD class                         M                        M
                          Max. continuous operating voltage (d.c.)  (UC)  15 V       33 V
        1               1´
                          Nominal current at 80 °C  (IL)    0.1 A                    0.1 A
        2               2´
                          D1 Total lightning impulse current (10/350 µs)  (Iimp)  10 kA  10 kA
                        protected  C2 Total nominal discharge current (8/20 µs)  (In)  20 kA  20 kA
                          Series resistance per line        13.8 ohm(s)              28.8  ohm(s)
        3               3´
                          Cut-off frequency line-PG  (fG)   0.85 MHz                 1.7 MHz
        4               4´
                                                            EAC, ATEX, IECEx,        CSA, EAC, ATEX, IECEx,
                          Approvals
                                                            CSA & USA Hazloc, SIL    CSA & USA Hazloc, SIL
                         BXT ML4 BE HF 5
        920 370   BXT ML4 BE HF 5
                         Space-saving combined lightning current and surge arrester module with RFID LifeCheck for protecting four single lines sharing a common
        920 370   4013364109117  04 02 01 02   24 g
              211,00 €   reference potential as well as high-frequency transmissions without galvanic isolation.
                          Type BXT ...                      ML4 BE HF 5
                          Part No.                          920 370
                          SPD class                         M
                          Max. continuous operating voltage (d.c.)  (UC)  6.0 V
        1               1´
                          Nominal current at 45 °C  (IL)    1.0 A
        2               2´
                          D1 Total lightning impulse current (10/350 µs)  (Iimp)  10 kA
                        protected  C2 Total nominal discharge current (8/20 µs)  (In)  20 kA
                          Series resistance per line        1.0  ohm(s)
        3               3´
                          Cut-off frequency line-PG  (fG)   100.0 MHz
        4               4´
                          Approvals                         CSA, UL, EAC, ATEX, IECEx, CSA & USA Hazloc, SIL

                         BXT ML4 BD HF 5 / 24
        920 371   BXT ML4 BD HF 5
        920 375   BXT ML4 BD HF 24
                         Space-saving combined lightning current and surge arrester module with RFID LifeCheck for protecting two pairs in unearthed  high-
        920 371   4013364109094  04 02 01 02   24 g
              211,00 €   frequency bus systems or two-wire video transmission systems.
        920 375   4013364109100  04 02 01 02   24 g
              211,00 €
                          Type BXT ...                      ML4 BD HF 5              ML4 BD HF 24
                          Part No.                          920 371                  920 375
                          SPD class                         M                        M
                          Max. continuous operating voltage (d.c.)  (UC)  6.0 V      33 V
        1               1´
                          Nominal current at 45 °C  (IL)    1.0 A                    1.0 A
        2               2´
                          D1 Total lightning impulse current (10/350 µs)  (Iimp)  10 kA  10 kA
                        protected  C2 Total nominal discharge current (8/20 µs)  (In)  20 kA  20 kA
        3               3´  Series resistance per line      1.0  ohm(s)              1.0  ohm(s)
                          Cut-off frequency line-line  (fG)  100.0 MHz               100.0 MHz
        4               4´
                                                            CSA, UL, EAC, ATEX, IECEx,   CSA, UL, EAC, ATEX, IECEx,
                          Approvals
                                                            CSA & USA Hazloc, SIL    CSA & USA Hazloc, SIL