Page 167 - Surge-Protection-E_0.pdf
P. 167
Pluggable SPDs – DIN Rail Mounted
BXT ML4 BE 5 – BE 180 920 320 920 322 920 324 920 336 920 325 BXT ML4 BE 5
BXT ML4 BE 12
BXT ML4 BE 24
BXT ML4 BE 36
BXT ML4 BE 48
BXT ML4 BE 180
920 327 920 326 BXT ML4 BE 60
Space-saving combined lightning current and surge arrester module with RFID LifeCheck for protecting four single lines sharing a common
reference potential as well as unbalanced interfaces. 920 320 920 322 4013364109032 04 02 01 02 24 g 24 g
206,10 €
4013364109049 04 02 01 02
920 324 206,10 € 4013364109056 04 02 01 02 38 g
202,20 €
920 336 4013364118539 04 02 01 02 40 g
237,10 €
920 325 4013364109063 04 02 01 02 24 g
206,10 €
920 326 920 327 4013364109070 04 02 01 02 24 g 24 g
206,10 €
General technical data: 206,10 €
4013364109087 04 02 01 02
D1 Total lightning impulse current (10/350 µs) (Iimp) 10 kA
C2 Total nominal discharge current (8/20 µs) (In) 20 kA
Type BXT ... ML4 BE 5 ML4 BE 12 ML4 BE 24 ML4 BE 36
Part No. 920 320 920 322 920 324 920 336
SPD class M M M M
Max. continuous operating voltage (d.c.) (UC) 6 V 15 V 33 V 45 V 1 1´
Nominal current at 45 °C (IL) 1.0 A 0.75 A 0.75 A 1.8 A 2 2´
Series resistance per line 1.0 ohm(s) 1.8 ohm(s) 1.8 ohm(s) 0.43 ohm(s) Pluggable SPDs – DIN Rail Mounted
Cut-off frequency line-PG (fG) 1.0 MHz 2.7 MHz 6.8 MHz 3.8 MHz protected
CSA, UL, EAC, ATEX, CSA, UL, EAC, ATEX, CSA, UL, EAC, ATEX, UL, EAC, ATEX, 3 3‘
Approvals IECEx, CSA & USA IECEx, CSA & USA IECEx, CSA & USA IECEx, CSA & USA 4 4‘
Hazloc, SIL Hazloc, SIL Hazloc, SIL Hazloc, SIL
Type BXT ... ML4 BE 48 ML4 BE 60 ML4 BE 180
Part No. 920 325 920 326 920 327
SPD class M M L
Max. continuous operating voltage (d.c.) (UC) 54 V 70 V 180 V
Nominal current at 45 °C (IL) 0.75 A 1.0 A 1.0 A
Series resistance per line 1.8 ohm(s) 1.0 ohm(s) 1.0 ohm(s)
Cut-off frequency line-PG (fG) 8.7 MHz 9.0 MHz 25.0 MHz
CSA, UL, EAC, ATEX, CSA, UL, EAC, ATEX, CSA, UL, EAC,
Approvals IECEx, CSA & USA IECEx, CSA & USA ATEX, IECEx, CSA & USA
Hazloc, SIL Hazloc, SIL Hazloc, SIL
BXT ML4 BD 5 – BD 180 920 340 920 342 920 344 920 345 920 346 920 347 BXT ML4 BD 5
BXT ML4 BD 12
BXT ML4 BD 24
BXT ML4 BD 48
BXT ML4 BD 60
BXT ML4 BD 180
Space-saving combined lightning current and surge arrester module with RFID LifeCheck for protecting two pairs of unearthed balanced
interfaces. 920 340 920 342 4013364108967 04 02 01 02 23 g 23 g
194,20 €
4013364108974 04 02 01 02
920 344 194,20 € 4013364108981 04 02 01 02 37 g
190,60 €
920 345 4013364108998 04 02 01 02 24 g
194,20 €
920 346 920 347 4013364109001 04 02 01 02 24 g 24 g
194,20 €
General technical data: 194,20 €
4013364109018 04 02 01 02
D1 Total lightning impulse current (10/350 µs) (Iimp) 10 kA
C2 Total nominal discharge current (8/20 µs) (In) 20 kA
Approvals CSA, UL, EAC, ATEX, IECEx, CSA & USA Hazloc, SIL 1 1´
Type BXT ... ML4 BD 5 ML4 BD 12 ML4 BD 24 2 2´
Part No. 920 340 920 342 920 344 protected
SPD class M M M
3 3´
Max. continuous operating voltage (d.c.) (UC) 6.0 V 15 V 33 V
Nominal current at 45 °C (IL) 1.0 A 1.0 A 1.0 A 4 4´
Series resistance per line 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s)
Cut-off frequency line-line (fG) 1.0 MHz 2.8 MHz 7.8 MHz
Type BXT ... ML4 BD 48 ML4 BD 60 ML4 BD 180
Part No. 920 345 920 346 920 347
SPD class M M L
Max. continuous operating voltage (d.c.) (UC) 54 V 70 V 180 V
Nominal current at 45 °C (IL) 1.0 A 1.0 A 0.75 A
Series resistance per line 1.0 ohm(s) 1.0 ohm(s) 1.8 ohm(s)
Cut-off frequency line-line (fG) 8.7 MHz 11.0 MHz 25.0 MHz
BXT ML4 BPD 24 920 314 BXT ML4 BPD 24
Space-saving combined arrester module with RFID LifeCheck for protecting two pairs in 24 V d.c. systems. Can also be used for systems with
earthed negative poles. Integrated PTC resistors allow the arrester to be safely reset after the system circuit has been affected by short-circuit 920 314 4013364261396 04 02 01 02 25 g
187,50 €
currents up to 40 A.
Type BXT ... ML4 BPD 24
Part No. 920 314
SPD class M 1 1´
Max. continuous operating voltage (d.c.) (UC) 33 V
2 2´
Nominal current at 70 °C (IL) 0.1 A
D1 Total lightning impulse current (10/350 µs) (Iimp) 10 kA protected
C2 Total nominal discharge current (8/20 µs) (In) 20 kA 3 3´
Series resistance per line typ. 10 ohm(s)
4 4´
Cut-off frequency line-line (fG) 4 MHz
Approvals EAC, SIL
Valid as of August 1, 2020 You will find detailed product information on our website 163