Page 174 - Surge-Protection-E_0.pdf
P. 174

Pluggable SPDs – DIN Rail Mounted


        BLITZDUCTOR SP
                                                             • Universal surge arrester
                                                                  – Universal surge arrester for two-pole, three-pole or four-pole
                                                                interfaces
                                                                  – High discharge capacity up to 20 kA (8/20 µs)
                                                                  – Low voltage protection level, capable of protecting terminal
                                                                equipment
                                                             • Arrester consists of a protection module and a base part
                                                                  – Easy replacement of protection modules
                                                                  – All protection components integrated in the protection module
   Pluggable SPDs –   DIN Rail Mounted                       • Functional and attractive design
                                                                  – Two universal base parts with or without signal disconnection

                                                                  – DIN rail mounted device with integrated earthing
                                                                  – Minimum space requirements, four single lines or two pairs
                                                                over a width 12 mm
                                                                  – Vibration and shock-tested for safe operation




        Pluggable and universal multipole surge arrester for use in information technology
        systems.

        BLITZDUCTOR SP arresters are pluggable and universal multipole DIN rail   For safe operation, the arrester is vibration and shock tested and resists
        mounted surge arresters for protecting measuring and control circuits, bus   up to 30 times the acceleration of gravity. The function-optimised arrester
        systems, emergency alarm systems or telecommunication systems.   design ensures both fast and easy replacement of the protection modules
        BLITZDUCTOR SP arresters combine a permanently high impulse current   which house all relevant protection elements.
        discharge capacity with an extremely low voltage protection level, thus   A wide range of accessories, e.g. for earthing unused lines or easily testing
        ensuring effective protection of terminal equipment even in case of inter-  lines round off the product range.
        ference caused by impulse currents and surges resulting from switching   The protection module and base part have to be ordered separately!
        operations.











        Two-part design comprising a base   The module locking mechanism en -   All protection elements are integrat-  Two universal base parts with or with-
        part and a protection module.  sures that the module is vibration-   ed in the plug-in module.  out signal disconnection if the protec-
                                  proof and protected against polarity                  tion module is removed.
                                  reversal.



        BLITZDUCTOR SP – Protection Modules

        926 320   BSP M4 BE 5
        926 322   BSP M4 BE 12  BSP M4 BE 5 – BE 180
        926 324   BSP M4 BE 24
        926 325   BSP M4 BE 48
        926 327   BSP M4 BE 180
                         Space-saving surge arrester module for protecting four single lines sharing a common reference potential and unbalanced interfaces.
        926 320   4013364127159  04 02 01 04   22 g
              138,80 €
        926 322   4013364127166  04 02 01 04   22 g
              138,80 €
        926 324   4013364127173  04 02 01 04   21 g
              138,80 €
        926 325   4013364127180  04 02 01 04   22 g   General technical data:
              138,80 €
        926 327   4013364127203  04 02 01 04   22 g
              138,80 €
                          D1 Lightning impulse current (10/350 µs) per line  (Iimp)  1 kA
                          C2 Total nominal discharge current (8/20 µs)  (In)  20 kA
                          Type BSP ...                      M4 BE 5     M4 BE 12     M4 BE 24
                          Part No.                          926 320 (   926 322 (    926 324 (
                          SPD class                         Q           Q            Q
                          Max. continuous operating voltage (d.c.)  (UC)  6.0 V  15 V  33 V
                          Nominal current at 45 °C  (IL)    1.0 A       0.75 A       0.75 A
                          Cut-off frequency line-PG  (fG)   1.0 MHz     2.7 MHz      6.8 MHz
                          Approvals                         UL, CSA, SIL, EAC   UL, CSA, SIL, EAC   UL, CSA, SIL, EAC
        1               1‘
                          Type BSP ...                      M4 BE 48    M4 BE 180
        2               2‘
                        protected  Part No.                 926 325 (   926 327 (
                          SPD class                         Q           R
                          Max. continuous operating voltage (d.c.)  (UC)  54 V  180 V
        3               3‘
        4               4‘  Nominal current at 45 °C  (IL)  0.75 A      1.0 A
                          Cut-off frequency line-PG  (fG)   8.7 MHz     25.0 MHz
                          Approvals                         UL, CSA, SIL, EAC   UL, CSA, SIL, EAC
        170              You will find detailed product information on our website             Valid as of August 1, 2020