Pluggable SPDs – DIN Rail Mounted
BLITZDUCTOR XTU – Protection Modules with LifeCheck
BXTU ML4 BD 0-180 920 349 BXTU ML4 BD 0-180
Space-saving combined lightning current and surge arrester module with actiVsense technology and RFID LifeCheck for protecting two pairs
(same or different operating voltage) of balanced interfaces with galvanic isolation. 920 349 4013364126404 04 02 01 03 25 g
217,30 €
Type BXTU ... ML4 BD 0-180
Part No. 920 349
SPD class M
Max. continuous operating voltage (d.c.) (UC) 180 V
Permissible superimposed signal voltage (Usignal) ≤ +/- 5 V
1 1‘
Cut-off frequency line-line (Usignal, balanced 100 ohms) (fG) 50 MHz i U>U N
Nominal current at 80 °C (equal to max. short-circuit current) (IL) 100 mA 2 2‘ Pluggable SPDs – DIN Rail Mounted
i
D1 Total lightning impulse current (10/350 µs) (Iimp) 10 kA protected
3 3‘
C2 Total nominal discharge current (8/20 µs) (In) 20 kA i U>U N
Series resistance per line ≤ 10 ohms; typically 7.5 ohms 4 4‘
i
Approvals CSA, UL, EAC, SIL
BXTU ML2 BD S 0-180 920 249 BXTU ML2 BD S 0-180
Space-saving combined lightning current and surge arrester module with actiVsense technology and RFID LifeCheck for protecting one pair
of balanced interfaces with galvanic isolation. Direct or indirect shield earthing. 920 249 4013364127845 04 02 01 03 23 g
150,00 €
Type BXTU ... ML2 BD S 0-180
Part No. 920 249
SPD class M
Max. continuous operating voltage (d.c.) (UC) 180 V
Permissible superimposed signal voltage (Usignal) ≤ +/- 5 V 1 1‘
i U>U N
Cut-off frequency line-line (Usignal, balanced 100 ohms) (fG) 50 MHz
Nominal current at 80 °C (equal to max. short-circuit current) (IL) 100 mA 2 i 2‘
D1 Total lightning impulse current (10/350 µs) (Iimp) 9 kA protected
C2 Total nominal discharge current (8/20 µs) (In) 20 kA 3 3‘
Series resistance per line ≤ 10 ohms; typically 7.5 ohms 4 4‘
Approvals CSA, UL, EAC, SIL