SPDs for LSA Technology
DRL 10 B 907 400 DRL 10 B 180
Lightning current carrying DRL plug-in SPD block (10 pairs), expandable with DRL protective plug. Integrated disconnection block contacts
allow protected testing, measuring and patching. 907 400 4013364107557 04 02 04 01 65 g
119,70 €
Type DRL ... 10 B 180
Part No. 907 400
SPD class G
Max. continuous operating voltage (d.c.) (UC) 180 V
Nominal current (IL) 0.4 A IN
a 1 b 2 3 4 5 6 7 8 9 10
D1 Total lightning impulse current (10/350 µs) (Iimp) 5 kA
C2 Total nominal discharge current (8/20 µs) (In) 10 kA
Series resistance per line ≤ 0.005 ohms
Plugs into LSA disconnection block 2/10
Approvals EAC a’ b’ OUT
DRL 10 B FSD 907 401 DRL 10 B 180 FSD
Lightning current carrying DRL plug-in SPD block (10 pairs), expandable with DRL protective plug. Integrated disconnection block contacts
allow protected testing, measuring and patching. Arrester with fail-safe function and visual fault indicator. 907 401 4013364107564 04 02 04 01 69 g
148,00 €
Type DRL ... 10 B 180 FSD
Part No. 907 401
SPD class G
Fault indication visual, colour change
Max. continuous operating voltage (d.c.) (UC) 180 V
IN
Nominal current (IL) 0.4 A a 1 b 2 3 4 5 6 7 8 9 10 LSA Technology
D1 Total lightning impulse current (10/350 µs) (Iimp) 5 kA SPDs for
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 9
Series resistance per line ≤ 0.005 ohms
Plugs into LSA disconnection block 2/10 a’ b’ OUT
Approvals EAC
DRL RE
Single-stage protective plug (one pair) for signal circuits sharing a common potential. Earthing via EF 10 DRL earthing frame. For disconnec-
tion blocks or lightning current carrying DRL plug-in SPD blocks only.
General technical data:
SPD class O
D1 Total lightning impulse current (10/350 µs)
in combination with DRL 10 B... (Iimp) 5 kA
C2 Total nominal discharge current (8/20 µs)
in combination with DRL 10 B... (In) 10 kA 907 421 907 422 907 423 DRL RE 12 DRL RE 24 DRL RE 48
907 425 907 424 DRL RE 60 DRL RE 180
Plugs into LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block
Approvals EAC 907 421 4013364107618 04 02 04 01 4 g
907 422 34,80 € 4013364107625 04 02 04 01 4 g
34,20 €
907 423 4013364107632 04 02 04 01 4 g
34,80 €
907 424 4013364107649 04 02 04 01 4 g
34,80 €
907 425 4013364107656 04 02 04 01 3 g
34,80 €
Type DRL ... RE 12 RE 24 RE 48
Part No. 907 421 907 422 907 423
Max. continuous operating voltage (d.c.) (UC) 14 V 28 V 54 V
Nominal current (IL) 0.4 A 0.4 A 0.4 A
Series resistance per line 4.7 ohms 4.7 ohms 6.8 ohms
Cut-off frequency line-PG (fG) 2.7 MHz 4.5 MHz 7.35 MHz
Type DRL ... RE 60 RE 180 a a
Part No. 907 424 907 425
IN 9 OUT
Max. continuous operating voltage (d.c.) (UC) 70 V 180 V
Nominal current (IL) 0.4 A 0.1 A b b
Series resistance per line 6.8 ohms 4.7 ohms
Cut-off frequency line-PG (fG) 10.5 MHz 42 MHz
Valid as of August 1, 2020 You will find detailed product information on our website 197