Page 202 - Surge-Protection-E_0.pdf
P. 202

SPDs for LSA Technology

                         DRL RD
        907 441   DRL RD 12
        907 442   DRL RD 24  Single-stage protective plug (one pair) for galvanically isolated interfaces. To be mounted into EF 10 DRL earthing frames. Installation recom-
        907 443   DRL RD 48
        907 444   DRL RD 60
        907 445   DRL RD 110
                         mended only in combination with lightning current carrying DRL plug-in SPD block.
        907 441   4013364107694  04 02 04 01   4 g
              31,70 €
        907 442   4013364107700  04 02 04 01   3 g
              31,20 €     General technical data:
        907 443   4013364107717  04 02 04 01   4 g
              31,70 €
        907 444   4013364107724  04 02 04 01   3 g
              31,70 €
        907 445   4013364118461  04 02 04 01   3 g
                          SPD class                         O
              31,80 €
                          Nominal current  (IL)             0.4 A
                          D1 Total lightning impulse current (10/350 µs)    5 kA
                          in combination with DRL 10 B...  (Iimp)
                          C2 Total nominal discharge current (8/20 µs)    10 kA
                          in combination with DRL 10 B...  (In)
                          Plugs into                        LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block
                          Approvals                         EAC
                          Type DRL ...                      RD 12            RD 24            RD 48
                          Part No.                          907 441          907 442          907 443
                          Max. continuous operating voltage (d.c.)  (UC)  14 V  28 V          54 V
                          Series resistance per line        2.2 ohms         2.2 ohms         4.7 ohms
                          Cut-off frequency line-line  (fG)  2.7 MHz         5.4 MHz          7.8 MHz
                          Type DRL ...                      RD 60            RD 110
        a              a´
                          Part No.                          907 444          907 445
        IN             OUT
                          Max. continuous operating voltage (d.c.)  (UC)  70 V  180 V
                          Series resistance per line        4.7 ohms         4.7 ohms
        b              b´
                          Cut-off frequency line-line  (fG)  11 MHz          20 MHz
   SPDs for   LSA Technology  907 430   DRL PD 180  DRL PD
                         Single-stage protective plug with overcurrent protection (one pair) for ADSL, ISDN Uk0 or a/b lines. To be mounted into EF 10 DRL earthing
        907 430   4013364107670  04 02 04 01   4 g
              31,10 €    frames. Installation recommended only in combination with lightning current carrying DRL plug-in SPD block.
                          Type DRL ...                      PD 180
                          Part No.                          907 430
                          SPD class                         O
                          Max. continuous operating voltage (d.c.)  (UC)  180 V
                          Nominal current  (IL)             0.1 A
                          D1 Total lightning impulse current (10/350 µs)    5 kA
                          in combination with DRL 10 B...  (Iimp)
                          C2 Total nominal discharge current (8/20 µs)
                          in combination with DRL 10 B...  (In)
        a              a´                                   10 kA
                          Series resistance per line        10 ohms +/- 15%
        IN             OUT
                          Cut-off frequency line-line  (fG)  61 MHz
                          Plugs into                        LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
        b              b´
                          Approvals                         EAC


                         DRL HD
        907 470   DRL HD 24
                         Single-stage protective plug (1 pair) for high-frequency transmissions (e.g. ISDN U2m, S2m and S0). HD 5 type for RS 485 bus systems. To be
        907 470   4013364107663  04 02 04 01   4 g
              33,00 €    mounted into EF 10 DRL earthing frames. Installation recommended only in combination with lightning current carrying DRL plug-in SPD block.
                          Type DRL ...                      HD 24
                          Part No.                          907 470
                          SPD class                         O
                          Max. continuous operating voltage (d.c.)  (UC)  28 V
                          Nominal current  (IL)             0.4 A
                          D1 Total lightning impulse current (10/350 µs)
                          in combination with DRL 10 B...  (Iimp)  5 kA
                          C2 Total nominal discharge current (8/20 µs)
                          in combination with DRL 10 B...  (In)
        a              a´                                   10 kA
                          Series resistance per line        4.7 ohms
        IN             OUT
                          Cut-off frequency line-line  (fG)  94 MHz
        b              b´  Plugs into                       LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
                          Approvals                         EAC