Page 211 - Surge-Protection-E_0.pdf
P. 211
SPDs for Field Devices
DPI MD EX 929 960 929 965 DPI MD EX 24 M 2
DPI MD EX 24 N 2
Energy-coordinated two-stage surge arrester for protecting intrinsically safe measuring circuits and bus systems according to FISCO.
Cable glands are available as an accessory.
Type DPI ... MD EX 24 M 2 MD EX 24 N 2
Part No. 929 960 929 965 929 960 929 965 4013364098145 04 02 05 01 172 g 171 g
161,60 €
4013364360778 04 02 05 01
161,60 €
SPD class T T
Max. continuous operating voltage (d.c.) (UC) 34.8 V 34.8 V
Nominal current (IL) 0.5 A 0.5 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1 kA 1 kA
RD
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 10 kA
protected
Cut-off frequency line-line (fG) 7 MHz 7 MHz BK
M20 x 1.5 female thread / 1 /2-14 NPT female thread /
For mounting on (field / device side)
M20 x 1.5 male thread 1 /2-14 NPT male thread
Approvals EACEx, ATEX, IECEx, SIL ATEX, IECEx, SIL
9
DPI CD EXI 929 961 929 963 DPI CD EXI 24 M
DPI CD EXI 24 N
Surge arrester for protecting intrinsically safe measuring circuits and bus systems according to FISCO.
929 961 4013364101784 04 02 05 02 169 g
145,30 €
929 963 4013364101807 04 02 05 02 172 g
145,30 €
Type DPI ... CD EXI 24 M CD EXI 24 N
Part No. 929 961 929 963
SPD class T T
Max. continuous operating voltage (d.c.) (UC) 32 V 32 V
Nominal current (IL) 0.55 A 0.55 A
D1 Lightning impulse current (10/350 µs) line-PG (Iimp) 1 kA 1 kA
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 10 kA RD
Cut-off frequency line-line (fG) 67 MHz 67 MHz
For mounting on (field / device side) M20 x 1.5 male thread 1 /2-14 NPT male thread
EACEx, ATEX, IECEx, EACEx, ATEX, IECEx, BK
Approvals GNYE
CSA & USA Hazloc, SIL CSA & USA Hazloc, SIL
SPDs for Field Devices
DPI CD EXD 929 962 929 964 DPI CD EXD 24 M
DPI CD EXD 24 N
Surge arrester in a flameproof enclosure for protecting measuring circuits and bus systems in potentially explosive atmospheres.
Type DPI ... CD EXD 24 M CD EXD 24 N
Part No. 929 962 929 964 929 962 929 964 4013364101791 04 02 05 02 169 g 169 g
145,30 €
4013364101814 04 02 05 02
145,30 €
SPD class T T
Max. continuous operating voltage (d.c.) (UC) 32 V 32 V
Nominal current (IL) 0.55 A 0.55 A
D1 Lightning impulse current (10/350 µs) line-PG (Iimp) 1 kA 1 kA
C2 Total nominal discharge current (8/20 µs) (In) 10 kA 10 kA RD
Cut-off frequency line-line (fG) 67 MHz 67 MHz
For mounting on (field / device side) M20 x 1.5 male thread 1 /2-14 NPT male thread
EACEx, ATEX, IECEx, EACEx, ATEX, IECEx, BK
Approvals GNYE
CSA & USA Hazloc, SIL CSA & USA Hazloc, SIL
DPI CD HF EXD 929 971 DPI CD HF EXD 5 M
Surge arrester in a flameproof enclosure for protecting measuring circuits and bus systems with high-frequency signals in potentially explosive
atmospheres.
929 971 4013364120761 04 02 05 01 272 g
140,90 €
Type DPI ... CD HF EXD 5 M
Part No. 929 971
SPD class T
Max. continuous operating voltage (d.c.) (UC) 6 V
Nominal current at 80 °C (IL) 0.1 A RD
C2 Total nominal discharge current (8/20 µs) (In) 20 kA
Cut-off frequency line-line (fG) 100 MHz
BL
For mounting on (field / device side) M20 x 1.5 male thread GNYE
BK
Approvals EACEx, ATEX, IECEx, SIL BN
Valid as of August 1, 2020 You will find detailed product information on our website 207