Page 244 - Surge-Protection-E_0.pdf
P. 244

Measuring and Test Devices


        RFID LifeCheck SPD Test Devices
                                                             • SPD test device for preventive maintenance
                                                                  – The RFID LifeCheck monitoring device detects thermal or electrical
                                                                overload conditions of all components
                                                                  – To avoid imminent failure and thus system downtime, the protecti-
                                                                on module should be replaced as soon as possible
                                                             • Benefits of this type of SPD testing:
                                                                  – Extremely easy and within a matter of seconds
                                                                  – Detection of thermal or electrical pre-damage of all components










        Periodic inspection of installed arresters           Mode of operation of the LifeCheck diagnostic system
        During operation, an arrester may be overloaded by discharge processes
        that are outside the device specification. To ensure high system availabil-  SPD (transponder)  Reader
        ity, it is therefore important to subject arresters to regular tests.     Energy
        Maintenance tests and test intervals for lightning protection systems are
        specified in DIN EN 62305-3, supplement 3 (see table excerpt). However,   RFID    RFID
                                                                         trans-
        these periods are only standard-based minimum requirements.      ponder           reader
          Class of    Visual    Complete  Complete inspection      SPD                            evaluation
                                                                                                    unit
            SPD     inspection  inspection  of critical systems
           I and II   1 year     2 years       1 year
          III and IV   2 years   4 years       1 year
                                                                                  Data
        Visual inspections of arresters for information technology systems do not
        make sense since the status of the devices is not generally visible. For this   Communication principle between SPD and test device
        purpose, another method has to be chosen as is the case with complete
        inspections. In the past, measurement equipment was used to test arrest-
        ers. These measurements were very time consuming, required expertise   Information is read via a hand-held tester which houses the RFID reader.
        and did not provide sufficient information.          It contactlessly transmits electromagnetic energy to the transponder in
                                                             the SPD, reads out its status and displays it. Information is simple: "SPD
        Notification before the arrester fails               OK" or "Replace SPD!". A test can be conducted in a matter of seconds.
        The three-stage LifeCheck monitoring circuit with early warning function   When testing, the arrester must simply be pulled out of the base part by
        detects all protection elements of an arrester. It detects extreme electrical   its mechanical length (approx. 50 mm). When using the BXT BAS, signal
        or thermal load below their destruction limit. This can be read out in   availability is also guaranteed while testing.
        seconds and without contact using a reader with RFID technology. If the
        reader determines "LifeCheck OK", no extreme load was detected. In   This type of monitoring reliably detects thermal and electrical overload
        the opposite case, the module should be replaced as soon as possible in   of all components, typically before the arrester fails and limits the avail-
        order not to jeopardise the availability of the protected circuit.   ability of the system to be protected. In addition, no expertise is required
                                                             for testing. The reader also facilitates documentation of the test results
        Simplified check by LifeCheck                        which is mandatory to comply with the EN 62305-3 standard.
        BLITZDUCTOR XT with integrated LifeCheck is particularly easy to
        maintain. LifeCheck uses modern RFID (radio frequency identification)   The  test  data  (date,  time,  results)  of  all  arresters  are  saved  and  can
        technology for monitoring the protective circuit and for communication.   be transmitted to a PC via a USB interface for printing or storage.
        Regardless of system downtimes, LifeCheck allows quick and easy test-  Consequently, a higher degree of protection and availability is achieved
        ing of the arrester by means of the portable DRC LC M1+ and DRC LC   by means of LifeCheck-based preventive maintenance since overload of
        M3+ test units or stationary DRC SCM XT and DRC MCM XT condition   components is detected even before the protection of the system circuit
        monitoring unit.                                     fails.













        Intuitive operation and fast arrester   Hand-held snap-on sensor  Interval testing with DRC LC M3+.  Database function of DRC LC M3+.
        testing (M1+).





   Measuring and    Mess- und  Test Devices  Prüfgeräte  240   You will find detailed product information on our website   Valid as of August 1, 2020