Measuring and Test Devices
RFID LifeCheck SPD Test Devices
• SPD test device for preventive maintenance
– The RFID LifeCheck monitoring device detects thermal or electrical
overload conditions of all components
– To avoid imminent failure and thus system downtime, the protecti-
on module should be replaced as soon as possible
• Benefits of this type of SPD testing:
– Extremely easy and within a matter of seconds
– Detection of thermal or electrical pre-damage of all components
Periodic inspection of installed arresters Mode of operation of the LifeCheck diagnostic system
During operation, an arrester may be overloaded by discharge processes
that are outside the device specification. To ensure high system availabil- SPD (transponder) Reader
ity, it is therefore important to subject arresters to regular tests. Energy
Maintenance tests and test intervals for lightning protection systems are
specified in DIN EN 62305-3, supplement 3 (see table excerpt). However, RFID RFID
trans-
these periods are only standard-based minimum requirements. ponder reader
Class of Visual Complete Complete inspection SPD evaluation
unit
SPD inspection inspection of critical systems
I and II 1 year 2 years 1 year
III and IV 2 years 4 years 1 year
Data
Visual inspections of arresters for information technology systems do not
make sense since the status of the devices is not generally visible. For this Communication principle between SPD and test device
purpose, another method has to be chosen as is the case with complete
inspections. In the past, measurement equipment was used to test arrest-
ers. These measurements were very time consuming, required expertise Information is read via a hand-held tester which houses the RFID reader.
and did not provide sufficient information. It contactlessly transmits electromagnetic energy to the transponder in
the SPD, reads out its status and displays it. Information is simple: "SPD
Notification before the arrester fails OK" or "Replace SPD!". A test can be conducted in a matter of seconds.
The three-stage LifeCheck monitoring circuit with early warning function When testing, the arrester must simply be pulled out of the base part by
detects all protection elements of an arrester. It detects extreme electrical its mechanical length (approx. 50 mm). When using the BXT BAS, signal
or thermal load below their destruction limit. This can be read out in availability is also guaranteed while testing.
seconds and without contact using a reader with RFID technology. If the
reader determines "LifeCheck OK", no extreme load was detected. In This type of monitoring reliably detects thermal and electrical overload
the opposite case, the module should be replaced as soon as possible in of all components, typically before the arrester fails and limits the avail-
order not to jeopardise the availability of the protected circuit. ability of the system to be protected. In addition, no expertise is required
for testing. The reader also facilitates documentation of the test results
Simplified check by LifeCheck which is mandatory to comply with the EN 62305-3 standard.
BLITZDUCTOR XT with integrated LifeCheck is particularly easy to
maintain. LifeCheck uses modern RFID (radio frequency identification) The test data (date, time, results) of all arresters are saved and can
technology for monitoring the protective circuit and for communication. be transmitted to a PC via a USB interface for printing or storage.
Regardless of system downtimes, LifeCheck allows quick and easy test- Consequently, a higher degree of protection and availability is achieved
ing of the arrester by means of the portable DRC LC M1+ and DRC LC by means of LifeCheck-based preventive maintenance since overload of
M3+ test units or stationary DRC SCM XT and DRC MCM XT condition components is detected even before the protection of the system circuit
monitoring unit. fails.
Intuitive operation and fast arrester Hand-held snap-on sensor Interval testing with DRC LC M3+. Database function of DRC LC M3+.
testing (M1+).