Page 52 - Surge-Protection-E_0.pdf
P. 52

N-PE Lightning Current Arresters

                         DEHNgap M 255 (FM)
        961 101   DGP M 255
        961 105   DGP M 255 FM
                         Coordinated and modular single-pole N-PE lightning current arrester; FM version with floating remote signalling contact.
        961 101   4013364118676  04 01 01 14   315 g
              271,90 €
        961 105   4013364118683  04 01 01 14   320 g
              296,40 €
                          Type                              DGP M 255                DGP M 255 FM
                          Part No.                          961 101                  961 105
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I   type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)   255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  100 kA      100 kA
                          Voltage protection level  (UP)    ≤ 1.5 kV                 ≤ 1.5 kV
                          Approvals                         VDE, KEMA, UL            VDE, KEMA, UL
                          Type of remote signalling contact  —                       changeover contact


                         DEHNgap Maxi 1 255 S
        900 050   DGPM 1 255 S
                         Coordinated single-pole N-PE lightning current arrester for busbars.
        900 050   4013364107496  04 01 01 14   507 g
              297,50 €
                          Type                              DGPM 1 255 S
                          Part No.                          900 050
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  100 kA
                          Voltage protection level  (UP)    ≤ 2.5 kV (including 80 cm connecting cable)
                          Operating state monitoring        via DEHNsignal DSI E 3




        961 180   DGPM 1 255
        961 185   DGPM 1 255 FM  DEHNgap Maxi 1 255 (FM)
                         Coordinated single-pole N-PE lightning current arrester; FM version with floating remote signalling contact.
        961 180   4013364157323  04 01 01 14   370 g
              327,30 €
        961 185   4013364157330  04 01 01 14   370 g
              343,30 €
                          Type                              DGPM 1 255               DGPM 1 255 FM
                          Part No.                          961 180                  961 185
                          SPD according to EN 61643-11 / IEC 61643-11
                                                                                     type 1 + type 2 / class I + class II
                                                            type 1 + type 2 / class I + class II
    N-PE Lightning Current Arresters  Lightning impulse current (10/350 µs)  (Iimp)  100 kA  100 kA
                          Max. continuous operating voltage (a.c.)  (UC)
                                                            255 V (50 / 60 Hz)
                                                                                     255 V (50 / 60 Hz)
                                                                                     ≤ 1.5 kV
                                                            ≤ 1.5 kV
                          Voltage protection level  (UP)
                                                            —
                          Type of remote signalling contact
                                                                                     changeover contact
        961 160   DGPM 440
        961 165   DGPM 440 FM  DEHNgap Maxi 440 (FM)
                         Coordinated single-pole N-PE lightning current arrester; FM version with floating remote signalling contact.
        961 160   4013364116290  04 01 01 14   369 g
              349,70 €
        961 165   4013364116306  04 01 01 14   372 g
              365,70 €
                          Type                              DGPM 440                 DGPM 440 FM
                          Part No.                          961 160                  961 165
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I   type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  440 V (50 / 60 Hz)   440 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  100 kA      100 kA
                          Voltage protection level  (UP)    ≤ 2.5 kV                 ≤ 2.5 kV
                          Approvals                         UL                       UL
                          Type of remote signalling contact  —                       changeover contact
                         DEHNgap H M 255
        961 102   DGPH M 255
                         Modular single-pole N-PE lightning current arrester.
        961 102   4013364118690  04 01 01 14   284 g
              191,90 €
                          Type                              DGPH M 255
                          Part No.                          961 102
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  100 kA
                          Voltage protection level  (UP)    ≤ 4 kV










        48               You will find detailed product information on our website             Valid as of August 1, 2020
   47   48   49   50   51   52   53   54   55   56   57