Surge Arresters – Type 2


        DEHNguard modular for North America
                                            • Prewired complete unit consisting of a base part and plug-in protection modules
                                            • No need for additional overcurrent protection devices
                                            • Short circuit current rating (SCCR) 200 kA
                                            • ANSI/UL 1449 – 4  Ed. Open-Type 1 SPD
                                                           th
                                            • High discharge capacity due to heavy-duty zinc oxide varistors (Imax 50 kA 8x20 μs)
                                            • High reliability due to "Thermo Dynamic Control" SPD monitoring device











        DEHNguard SU 1P …:    Modular single-pole surge arrester for application in Single Phase electrical systems
        DEHNguard MU SP …:   Modular surge arrester for application in Split Phase systems
        DEHNguard MU SPN …:  Modular surge arrester for application in Split Phase systems (with N protected)
        DEHNguard MU CGD …:  Modular surge arrester for application in Corner Grounded Delta systems
        DEHNguard MU 3PY …:  Modular surge arrester for application in 3 Phase Wye electrical systems
        DEHNguard MU 3PD …:  Modular surge arrester for application in 3 Phase Delta electrical systems
        DEHNguard MU 3PH …:  Modular surge arrester for application in 3 Phase High-leg Delta systems
        DEHNguard … R:    With remote status indicator for monitoring device (Form C / SPDT contact)

        The DEHNguard SU/MU … surge arresters are  modular DIN rail mounted   ules. Each protective circuit of the multipole surge arresters and each
        SPDs in the functional Red/line family design and set new standards in   protection module are mechanically coded to guard against installing an
        terms of safety and user-friendliness. The SPDs are UL 1449 4th Edition   incorrect module.
        certified as Type 1 Component Assemblies and are designed for all com-  The dual “Thermo Dynamic Control” monitoring device was not only de-
        mon electrical power systems. These devices have optimised voltage pro-  veloped on the basis of national and international product standards, but
        tection ratings and therefore provide ideal surge protection for the United   also reflects decades of experience in the world market of surge protective
        States and Canadian electrical panel markets.        devices and considers practical applications where arresters might be
        The enhanced maximum discharge capacity of  50 kA, the high short cir-  damaged. As with all DEHN surge arresters with “Thermo Dynamic
        cuit current rating (SCCR) of 200 kA and the fact that there is no need for   Control”, the intensity of the discharge current and the surface tempera-
        additional overcurrent protection devices mean that the DEHNguard SU/  ture of the heavy-duty varistor are evaluated. The visual status indicator
        MU product family fulfils all the requirements of modern day electrical   with green and red indicator flags shows the availability of every protec-
        applications. Besides the variety of features shows that both reliable surge   tive circuit. Apart from this standard visual indication, DEHNguard M SU/
        protection and equipment safety are key elements of the modular   MU ... FM devices feature a Form C contact (SPDT).
        DEHNguard surge arresters. The application-based product designation   As the remote signalling contact is designed as a floating changeover
        makes it considerably easier to choose the correct device for the relevant   contact, the remote signal can, depending on the circuit concept, be used
        application as well as the module locking system firmly fixes the protec-  as a make or break contact. The surge arresters of the multipole modular
        tion modules to the base part. Neither vibration during transport nor the   DEHNguard MU family feature multifunctional terminals on a standard-
        enormous electromagnetic forces of discharge can loosen the protection   ised spacing of 1 module for the connection of wires and busbars, allow-
        modules. Nevertheless, they can be easily replaced without tools by simply
    Surge Arresters – Type 2  pressing the user-friendly module release button of the protection mod-  of applications can be easily connected in series for optimal protection.
                                                             ing easy wiring with other DIN rail mounted devices. Thus, a wide range





        908 300   DG MU 3PY 208 3W+G
        908 314   DG MU 3PY 480 3W+G  DEHNguard MU 3PY ... 3W+G
        908 301   DG MU 3PY 600 3W+G
                         DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Wye electrical
        908 300   4013364148680  04 01 02 17   303 g
              223,50 €   systems
        908 314   4013364148703  04 01 02 17   339 g
              223,50 €
        908 301   4013364148727  04 01 02 17   363 g
              223,50 €
                          Type DG MU ...                       3PY 208 3W+G    3PY 480 3W+G    3PY 600 3W+G
                          Part No.                             908 300         908 314         908 301
                          SPD classification acc. to ANSI/UL 1449 4  Ed.  Open-Type 1 SPD   Open-Type 1 SPD   Open-Type 1 SPD
                                                 th
                                                               Type 4-1 Component   Type 4-1 Component   Type 4-1 Component
                          SPD classification acc. to CSA - C22.2 No. 269.1-14
                                                               Assembly        Assembly        Assembly
                          Max. continuous operating voltage AC [L-G] / [L-L]  (MCOV)  180 V a.c. / 360 V a.c.   385 V a.c. / 770 V a.c.   510 V a.c. / 1020 V a.c.
                          Nominal discharge current (8x 20 µs)  (In)  20 kA    20 kA           20 kA
                          Max. discharge current (8/20)  (Imax)  50 kA         50 kA           50 kA
                          Voltage protection rating [L-G] / [L-L]  (VPR)  600 Vpk / 1200 Vpk   1200 Vpk / 2500 Vpk   1500 Vpk / 3000 Vpk
                          Max. mains-side overcurrent protection  Not needed   Not needed      Not needed
                          Approvals                            UL, CSA         UL, CSA         UL, CSA



        70               You will find detailed product information on our website             Valid as of August 1, 2020