Page 71 - Surge-Protection-E_0.pdf
P. 71

Surge Arresters – Type 2


           DEHNguard S ... VA
           • Multi-purpose surge arrester consisting of a base part
            and a plug-in protection module
           • Leakage-current-free series connection of a varistor
            and a spark gap in the pluggable protection module
           • High reliability due to "Thermo Dynamic Control" SPD
            monitoring device
           • Energy coordination with other arresters of the Red/Line
            product family
           • Easy replacement of protection modules without tools due
            to module locking system with module release button
           • Narrow (modular) design according to DIN 43880
           • Multifunctional terminal for connecting conductors
            and busbars
                                                                For protecting low-voltage consumer installations against surges. For installation
                                                                in conformity with the lightning protection zone concept at the boundaries from
                                                                0B – 1 and higher.


           DEHNguard S ... VA:   Modular single-pole surge arrester with a varistor connected in series with a spark gap in the pluggable protection
                            module
           DEHNguard S ... VA FM: Modular single-pole surge arrester with a varistor connected in series with a spark gap in the pluggable protection
                            module; with remote signalling contact for monitoring device (floating changeover contact)

           The single-pole DEHNguard S ... VA surge arresters are an ideal supple-  A high discharge capacity, complete absence of leakage currents, a low
           ment to the proven DEHNguard product families. The special series con-  voltage protection level and the dual “Thermo Dynamic Control” moni-
           nection of a spark gap and a varistor in the protection module opens up   toring and disconnection device describe the high level of device safety.
           new fields of application. It is advisable to use DEHNguard S ... VA devic-  The DEHN-specific “Thermo Dynamic Control” disconnector ensures that
           es to protect, for example, systems with permanent insulation monitoring   the arresters enter a safe and isolated state, even in case of extreme
           and the traction power lines in railway systems where complete absence   overload. For this purpose, the surface temperature of the heavy-duty
           of leakage currents is required. DEHNguard S ... VA surge arresters are also   varistor and the intensity of the discharge current are used for evaluation.
           suited for protecting power line communication systems.  In addition to the standard visual indication with red and green indicator
           Multifunctional terminals provide almost unlimited flexibility in terms of   flags, the DEHNguard S VA ... FM devices feature a three-pole remote
           connection to one another, but also to other DIN rail mounted devices on   signalling terminal. As the remote signalling contact is designed as a float-
           the distribution board. However, it is not only flexibility that characterises   ing changeover contact, the remote signal can, depending on the circuit
           the DEHNguard S ... VA family. Its distinctive performance parameters set   concept, be used as a make or break contact.
           standards worldwide:

           DEHNguard S VA                                                                                   952 080  952 082  952 084   DG S 75 VA
                                                                                                             DG S 275 VA
                                                                                                             DG S 385 VA
           Modular single-pole surge arrester with a varistor connected in series with a spark gap in the pluggable protection module.
                                                                                                            952 080   4013364127296  04 01 02 04   107 g
                                                                                                              952 082          102,20 € 4013364127319  04 01 02 04   113 g
                                                                                                             97,30 €
           Type DG S ...                     75 VA            275 VA           385 VA                       952 084        4013364127333  04 01 02 04   117 g
                                                                                                             102,20 €
           Part No.                          952 080          952 082          952 084
           SPD according to EN 61643-11 / IEC 61643-11  type 2 / class II   type 2 / class II   type 2 / class II
           Max. continuous operating voltage (a.c.)  (UC)  75 V (50 / 60 Hz)   275 V (50 / 60 Hz)   385 V (50 / 60 Hz)
           Nominal discharge current (8/20 µs)  (In)  10 kA   10 kA            10 kA
           Max. discharge current (8/20 µs)  (Imax)  20 kA    20 kA            20 kA
           Voltage protection level  (UP)    ≤ 1.1 kV         ≤ 1.5 kV         ≤ 1.75 kV                              Surge Arresters – Type 2
           Max. mains-side overcurrent protection  100 A gG   100 A gG         100 A gG
           DEHNguard S VA FM                                                                                952 085  952 087  952 089   DG S 75 VA FM
                                                                                                             DG S 275 VA FM
                                                                                                             DG S 385 VA FM
           Modular single-pole surge arrester with a varistor connected in series with a spark gap in the pluggable protection module;
           with floating remote signalling contact.                                                         952 085    952 087     4013364127302  04 01 02 04   111 g  116 g
                                                                                                             115,40 €
                                                                                                             4013364127326  04 01 02 04
                                                                                                            952 089        110,50 € 4013364127340  04 01 02 04   121 g
                                                                                                                  115,40 €
           Type DG S ...                     75 VA FM         275 VA FM        385 VA FM
           Part No.                          952 085          952 087          952 089
           SPD according to EN 61643-11 / IEC 61643-11  type 2 / class II   type 2 / class II   type 2 / class II
           Max. continuous operating voltage (a.c.)  (UC)  75 V (50 / 60 Hz)   275 V (50 / 60 Hz)   385 V (50 / 60 Hz)
           Nominal discharge current (8/20 µs)  (In)  10 kA   10 kA            10 kA
           Max. discharge current (8/20 µs)  (Imax)  20 kA    20 kA            20 kA
           Voltage protection level  (UP)    ≤ 1.1 kV         ≤ 1.5 kV         ≤ 1.75 kV
           Max. mains-side overcurrent protection  100 A gG   100 A gG         100 A gG
           Accessories for DEHNguard S ... VA

           Varistor-Based Protection Module for DEHNguard S ... VA                                          952 025  952 027  952 029   DG MOD 75 VA
                                                                                                             DG MOD 275 VA
                                                                                                             DG MOD 385 VA
           Protection module for DEHNguard S ... VA arresters comprising a varistor connected in series with a spark gap.
                                                                                                            952 025   4013364127357  04 01 02 04   34 g
                                                                                                              952 027          86,80 € 4013364127364  04 01 02 04   40 g
           Type                              DG MOD 75 VA     DG MOD 275 VA    DG MOD 385 VA                952 029        4013364127371  04 01 02 04   44 g
                                                                                                             81,90 €
                                                                                                             86,80 €
           Part No.                          952 025          952 027          952 029
           Max. continuous operating voltage (a.c.)  (UC)  75 V  275 V         385 V
           Valid as of August 1, 2020                         You will find detailed product information on our website   67
   66   67   68   69   70   71   72   73   74   75   76