Page 90 - Surge-Protection-E_0.pdf
P. 90

Surge Arresters – Type 2 for PV Systems

        952 513   DG M YPV SCI 150
        952 511   DG M YPV SCI 600
        952 510   DG M YPV SCI 1000  DEHNguard M YPV SCI ...
        952 512   DG M YPV SCI 1200
                         Modular multipole surge arrester with three-step d.c. switching device for use in PV systems
        952 513   4013364136663  04 01 02 07   269 g
              226,10 €
        952 511   4013364127494  04 01 02 07   291 g
              218,70 €
        952 510   4013364126428  04 01 02 07   340 g
              226,10 €
        952 512   4013364127951  04 01 02 07   336 g
              257,60 €    Type DG ...                 M YPV SCI 150  M YPV SCI 600  M YPV SCI 1000  M YPV SCI 1200
                          Part No.                    952 513       952 511       952 510       952 512
                          SPD according to EN 50539-11  type 2      type 2        type 2        type 2
                          Max. PV voltage  (UCPV)     150 V         600 V         1000 V        1200 V
                          Short-circuit current rating  (ISCPV)  10 kA  10 kA     10 kA         10 kA
                          Nominal discharge current (8/20 µs)   10 kA  12.5 kA    12.5 kA       12.5 kA
                               [(DC+/DC-) --> PE]  (In)
                          Max. discharge current (8/20 µs)   20 kA  25 kA         25 kA         25 kA
                               [(DC+/DC-) --> PE]  (Imax)
                          Voltage protection level  (UP)  ≤ 0.8 kV  ≤ 2.5 kV      ≤ 4 kV        ≤ 4.5 kV
                          Approvals                   KEMA, UL, CSA   KEMA, UL, CSA   KEMA, UL, CSA   KEMA, CSA
        952 518   DG M YPV SCI 150 FM
        952 516   DG M YPV SCI 600 FM
        952 515   DG M YPV SCI 1000 FM  DEHNguard M YPV SCI ... FM
        952 517   DG M YPV SCI 1200 FM
                         Modular multipole surge arrester with three-step d.c. switching device for use in PV systems;
        952 518   4013364136670  04 01 02 07   276 g
              265,70 €   with remote signalling contact for monitoring device (floating changeover contact).
        952 516   4013364127500  04 01 02 07   298 g
              258,30 €
        952 515   4013364126435  04 01 02 07   323 g
              265,70 €
        952 517   4013364127968  04 01 02 07   338 g
              297,20 €
                          Type DG ...                 M YPV SCI 150 FM M YPV SCI 600 FM M YPV SCI 1000 FM M YPV SCI 1200 FM
                          Part No.                    952 518       952 516       952 515       952 517
                          SPD according to EN 50539-11  type 2      type 2        type 2        type 2
                          Max. PV voltage  (UCPV)     150 V         600 V         1000 V        1200 V
                          Short-circuit current rating  (ISCPV)  10 kA  10 kA     10 kA         10 kA
                          Nominal discharge current (8/20 µs)
                               [(DC+/DC-) --> PE]  (In)  10 kA      12.5 kA       12.5 kA       12.5 kA
                          Max. discharge current (8/20 µs)   20 kA  25 kA         25 kA         25 kA
                               [(DC+/DC-) --> PE]  (Imax)
                          Voltage protection level  (UP)  ≤ 0.8 kV  ≤ 2.5 kV      ≤ 4 kV        ≤ 4.5 kV
                          Approvals                   KEMA, UL, CSA   KEMA, UL, CSA   KEMA, UL, CSA   KEMA, CSA
                          Type of remote signalling contact  changeover contact   changeover contact   changeover contact   changeover contact
        952 551   DG S PV SCI 150
        952 550   DG S PV SCI 600  DEHNguard S PV SCI ...
                         Modular single-pole surge arrester with three-step d.c. switching device for PV systems earthed on the d.c. side.
        952 551   4013364136687  04 01 02 07   182 g
              149,20 €
        952 550   4013364136502  04 01 02 07   200 g
              141,80 €
                          Type DG ...                 S PV SCI 150                S PV SCI 600
                          Part No.                    952 551                     952 550
                          SPD according to EN 50539-11  type 2                    type 2
                          Max. PV voltage  (UCPV)     150 V                       600 V
                          Short-circuit current rating  (ISCPV)  10 kA            10 kA
                          Nominal discharge current (8/20 µs)
                               [(DC+/DC-) --> PE]  (In)  10 kA                    12.5 kA
                          Max. discharge current (8/20 µs)
                               [(DC+/DC-) --> PE]  (Imax)  20 kA                  25 kA
    Surge Arresters – Type 2  Approvals               KEMA, UL, CSA               KEMA, UL, CSA
                                                      ≤ 0.8 kV
                                                                                  ≤ 2.5 kV
                          Voltage protection level  (UP)
                         DEHNguard S PV SCI ... FM
        952 556
          DG S PV SCI 150 FM
          DG S PV SCI 600 FM
        952 555
                         Modular single-pole surge arrester with three-step d.c. switching device for PV systems earthed on the d.c. side;
        952 556   4013364136694  04 01 02 07   187 g
              175,10 €   with remote signalling contact for monitoring device (floating changeover contact).
        952 555   4013364136519  04 01 02 07   203 g
              168,00 €
                          Type DG ...                 S PV SCI 150 FM             S PV SCI 600 FM
                          Part No.                    952 556                     952 555
                          SPD according to EN 50539-11  type 2                    type 2
                          Max. PV voltage  (UCPV)     150 V                       600 V
                          Short-circuit current rating  (ISCPV)  10 kA            10 kA
                          Nominal discharge current (8/20 µs)   10 kA             12.5 kA
                               [(DC+/DC-) --> PE]  (In)
                          Max. discharge current (8/20 µs)   20 kA                25 kA
                               [(DC+/DC-) --> PE]  (Imax)
                          Voltage protection level  (UP)  ≤ 0.8 kV                ≤ 2.5 kV
                          Approvals                   KEMA, UL, CSA               KEMA, UL, CSA
                          Type of remote signalling contact  changeover contact   changeover contact