Page 88 - Surge-Protection-E_0.pdf
P. 88
Surge Arresters – Type 2 for PV Systems
DEHNguard modular YPV ... FM
Multipole photovoltaic arresters
• Prewired complete unit for photovoltaic systems consisting
of a base part and plug-in protection modules
• Fault-resistant Y circuit with three heavy-duty varistors
prevents damage to the surge protective device in case
of insulation faults in the generator circuit
• Tested to EN 50539-11
• High reliability due to “Thermo Dynamic Control” disconnector
• Fault indication by red indicator flag in the inspection window
• Suitable for use in accordance with IEC 60364-7-712
[Photovoltaic (PV) power systems]
For protecting low-voltage consumer installations against surges. For use in accord-
ance with IEC 60364-7-712 [photovoltaic (PV) power systems].
DEHNguard M YPV 1200 FM: For PV systems up to 1170 V, with remote signalling contact for monitoring device (floating changeover contact)
DEHNguard M YPV 1500 FM: For PV systems up to 1500 V, with remote signalling contact for monitoring device (floating changeover contact)
The modular DEHNguard modular YPV SCI ... FM surge arresters are spe- The fault-resistant Y circuit with three heavy-duty varistors prevents dam-
cifically designed for protecting equipment in photovoltaic systems. The age to surge protective devices in case of insulation faults in the genera-
devices are available for 1200 V and 1500 V and cover the most common tor circuit of the photovoltaic generator.
voltage levels. The green and red indicator flags show the availability of every protective
The following application features distinguish the modular arrester design circuit. Apart from this visual indication, DEHNguard YPV ... FM arresters
of this Red/Line product series. The module locking system firmly fixes the also feature a three-pole remote signalling terminal. As the remote signal-
protection modules to the base part. Neither shock nor vibration nor the ling contact is designed as a floating changeover contact, the remote
enormous forces of discharge affect the safe connection to the protection signal can, depending on the circuit concept, be used as a make or break
module. Nevertheless, the protection modules can be easily replaced with- contact. As with all surge arresters of the modular DEHNguard modular
out tools by simply pressing the easy-to-use module release button of the family, DEHNguard modular YPV ... FM arresters incorporate multifunc-
protection modules. Every protective path of DEHNguard modular YPV SCI tional terminals on a standardised spacing of 1 module for connecting
... FM and every protection module is mechanically coded to guard against conductors and busbars, allowing easy wiring with other DIN rail mount-
installing the incorrect module. ed devices.
DEHNguard M YPV ... FM
952 565 DG M YPV 1200 FM
952 567 DG M YPV 1500 FM
Modular multipole surge arrester for PV systems with remote signalling contact for monitoring device (floating changeover contact).
952 565 4013364327719 04 01 02 22 300 g
248,60 €
952 567 4013364327726 04 01 02 22 329 g
273,50 €
Type DG M YPV ... 1200 FM 1500 FM
Part No. 952 565 952 567
SPD according to EN 50539-11 type 2 type 2
1170 V
1500 V
Max. PV voltage (UCPV)
Surge Arresters – Type 2 Short-circuit current rating (ISCPV) 10 kA 10 kA
15 kA
20 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In)
40 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax)
40 kA
Voltage protection level (UP)
≤ 5 kV
≤ 4 kV
Approvals
changeover contact
Type of remote signalling contact UL, KEMA UL, KEMA
changeover contact
Accessories for DEHNguard modular YPV ... FM
Varistor-Based Protection Module for DEHNguard M YPV
952 048 DG MOD H PV 600
952 049 DG MOD H PV 750
Type DG MOD H PV 600 DG MOD H PV 750
952 048 4013364327733 04 01 02 22 51 g
Part No. 952 048 952 049
62,70 €
952 049 4013364327740 04 01 02 22 60 g
70,90 €
Max. continuous operating voltage (d.c.) (UC) 600 V 750 V
84 You will find detailed product information on our website Valid as of August 1, 2020