Page 94 - Surge-Protection-E_0.pdf
P. 94

Surge Arresters – Type 2 for PV Systems


        DEHNguard YPV SCI ... – compact
                                                             Compact PV arrester with three-step d.c. switching device
                                                             •  Prewired complete unit for use in photovoltaic systems
                                                             •  Combined disconnection and short-circuiting device with safe
                                                               electrical isolation (patented SCI principle)
                                                             •  Tried and tested fault-resistant Y circuit of  DEHNguard
                                                               YPV SCI ... prevents damage to the surge protective device
                                                               in case of insulation faults in the generator circuit
                                                             •  Tested to EN 50539-11
                                                             •  Suitable for use in all PV systems according to IEC 60364-7-712





        For protecting low-voltage consumer installations against surges. For use in accord-
        ance with IEC 60364-7-712 (photovoltaic (PV) power systems).



        DEHNguard YPV SCI 600 / 1000: Multipole surge arrester with three-step d.c. switching device; for photovoltaic systems up to 600 / 1000 V
        DEHNguard YPV SCI ... FM:    With remote signalling contact for monitoring device (floating changeover contact)




        The DEHNguard YPV SCI ... surge arresters are specifically designed for   DEHNguard YPV SCI ... is a special cost-effective and application-opti-
        protecting equipment in photovoltaic systems. The patented three-step   mised device which is particularly designed for string inverter systems
        d.c. switching device (SCI principle) makes these arresters particularly safe   with a limited system current up to 1000 A. The design includes the main
        so that they fulfil all requirements in modern photovoltaic systems. The   device features without compromising safety.
        devices are available as 600 V and 1000 V versions and cover the most   The green and red indicator flags show the availability of every protective
        common voltage levels for string inverter systems.   circuit. Apart from this visual indication, DEHNguard YPV SCI ... (FM) ar-
        To fulfil the special requirements in photovoltaic systems, a fault-resistant   resters also feature a three-pole remote signalling terminal. As the remote
        Y circuit consisting of three protective paths of the varistor and a com-  signalling contact is designed as a floating changeover contact, the re-
        bined disconnection and short-circuiting device are integrated in a single   mote signal can, depending on the circuit concept, be used as a make or
        device.                                              break contact.
        This synergy further reduces the probability of an arrester failure in case
        of the operating and fault states which have to be considered in photo-  Switching stages
        voltaic systems. This ensures that the arrester is protected in case of over-
        load. Even in case of voltages up to 1000 V d.c., a switching arc, which is   1.   2.   3.
                                                                             Tripping of the  Active
                                                                                               Safe
        likely to occur when a conventional disconnector (for a.c. applications) of   Original   disconnection  arc   electrical
        a surge protective device is triggered, is extinguished immediately without   state  device  extinction  isolation
        risk.



    Surge Arresters – Type 2                                 Three-step d.c. switching device (patented SCI principle)  SCI
                                                                           SCI
                                                                                            SCI
                                                                                   SCI



                         DEHNguard compact YPV SCI ... FM
                950 536   DG YPV SCI 600 FM
                950 535   DG YPV SCI 1000 FM
                         Multipole surge arrester with three-step d.c. switching device for use in PV systems,
                950 536   4013364154995  04 01 02 09      285 g   with remote signalling contact for monitoring device (floating changeover contact).
                      191,30 €
                950 535   4013364154988  04 01 02 09      310 g
                      195,60 €
        950 531   DG YPV SCI 600
        950 530   DG YPV SCI 1000
                          Type DG YPV SCI ...                 600         600 FM      1000        1000 FM
                          Part No.                            950 531     950 536     950 530     950 535
        950 531   4013364152953  04 01 02 09      275 g
              152,00 €
        950 530   4013364152960  04 01 02 09      300 g
              156,30 €
                          SPD according to EN 50539-11        type 2      type 2      type 2      type 2
                          Max. PV voltage  (UCPV)             600 V       600 V       1000 V      1000 V
                          Short-circuit current rating  (ISCPV)  1000 A   1000 A      1000 A      1000 A
                          Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE]  (In)  12.5 kA  12.5 kA  12.5 kA  12.5 kA
                          Max. discharge current (8/20 µs) [(DC+/DC-) --> PE]  (Imax)  25 kA  25 kA  25 kA  25 kA
                          Voltage protection level  (UP)      ≤ 2.5 kV    ≤ 2.5 kV    ≤ 4 kV      ≤ 4 kV
                          Approvals                           KEMA, UL    KEMA, UL    KEMA, UL    KEMA, UL
                          Type of remote signalling contact   ––          changeover contact  ––  changeover contact



        90               You will find detailed product information on our website             Valid as of August 1, 2020