COMPATIBILITY OF ACCESSORIES






                                   POSITION OF INTERNAL ACCESSORIES FOR THE TMAX XT5


                    With 4-pole circuit-breakers, it is not possible to add accessories to the fourth pole.




                     YO/YU                        KLC on CB                   1Q+1SY








                     2Q+1SY                       3Q+1SY                      1S51






                                                                              Ekip COM /
                     1S52 (1)                     2Q 400V                     Ekip COM
                                                                              STA /
                                                                                 (2)
                                                                              Micro I/O




                     Ekip 1K /                    1Q+1SY                      1Q+1SY
                     Ekip MM  (3)                 le   (4)                    400V (4)




                    (1) YO or YU must be mounted on the third pole to make S52 signaling available.
                    (2) Ekip COM or stand-alone module, depending on the trip unit.
                    (3) Available for the Ekip Touch and Ekip Hi-Touch only.
                    (4) Available for the TM trip unit, Ekip Dip trip unit and switch-disconnector only.





                                                  READING INFORMATION

                Glossary       Discription                      Glossary        Discription
                 YO            : Shunt opening release           S52            : Contact signaling YO/YU tripping
                 YU            : Undervoltage release            Ekip COM       : Ekip Communication module
                 KLC on CB     : Keylock device on circuit breaker  Ekip COM STA  : Ekip Communication module stand-alone
                 Q             : Contact signaling open/closed   Micro I/O      : Module for Touch and Hi-Touch trip unit
                 SY            : Contact signaling tripping      Ekip 1K        : Ekip 1K signaling
                 S51           : Contact signaling tripping due to trip unit  Ekip MM  : Ekip Maintenance Module