NON-AUTO AIR CIRCUIT BREAKERS
         TECHNICAL DATA



         Common data
         Rated service voltage Ue  [V]  690
         Rated insulation voltage Ui  [V]  1000
         Rated impulse withstand voltage   [kV]  12
         Uimp
         Frequency               [Hz]  50 - 60
         Number of poles               3- 4
         Version                       Fixed - Withdrawable
         Suitable for isolation according to  IEC 60947-3




                                                                                                                  ACB & ARC
                                                                                                                  DETECTION
         SACE Emax 2                                 E1.2       E2.2             E4.2            E6.2
         Performance levels                          N/MS       N/MS   H/MS      N/MS  H/MS      H/MS
         Rated uninterrupted current Iu @ 40°C  [A]  250        800    800       3200  3200      4000
                                            [A]      630        1000   1000      4000  4000      5000
                                            [A]      800        1250   1250                      6300
                                            [A]      1000       1600   1600
                                            [A]      1250       2000   2000
                                            [A]      1600       2500   2500
         Neutral pole current-carrying capacity for 4-pole CBs  [%Iu]  100  100  100  100  100   50-100
         Rated short-time   (1s)            [kA]     50         66     85        66    85        100
         withstand current Icw  (3s)        [kA]     30         50     66        50    75  1)    100
         Rated short-circuit making 400-415 V  [kA]  105        145    187       145   187       220
         capacity (peak value) Icm
                          690 V             [kA]     105        145    187       145   187       220
         Utilization category (according to IEC 60947-3)  AC-23A  AC-23A  AC-23A  AC-23A  AC-23A  AC-23A
         Dimensions       H - Fixed / Withdrawable  [mm]  296/363.5  371/425 371/425  371/425 371/425  371/425
                          D - Fixed / Withdrawable  [mm]  183/271  270/383 270/383  270/383 270/383  270/383
                          W - Fixed 3p/4p/4p FS  [mm]           276/366          384/510         762/888/1014
                          W - Withdrawable 3p/4p/4p FS [mm]     317/407          425/551         803/929/1069
         1)  E4.2H/MS 3200A: 66KA Icw (3s)















         SACE Emax 2                                 E1.2       E2.2             E4.2            E6.2
         Mechanical life with regular ordinary  [Iu]  1000  1600 1600  2000  2500 < 2500  2500  4000 4000  6300
         maintenance prescribed by the manufacturer  [No. cycles  20  20  25  25  20  20  20  15  12       12
                                            x 1000]
                          Frequency         [Oper./  60     60  60     60    60  60    60    60  60        60
                                            Hour]
         Electrical life with regular 690 V  [No. cycles  6.5  6.5  10  8    7   10    8     4   4         2
         ordinary maintenance               x 1000]
         prescribed by the   Frequency      [Oper./  30     30  30     30    30  20    20    20  10        10
          manufacturer                      Hour]