NON-AUTO AIR CIRCUIT BREAKERS
TECHNICAL DATA
Common data
Rated service voltage Ue [V] 690
Rated insulation voltage Ui [V] 1000
Rated impulse withstand voltage [kV] 12
Uimp
Frequency [Hz] 50 - 60
Number of poles 3- 4
Version Fixed - Withdrawable
Suitable for isolation according to IEC 60947-3
ACB & ARC
DETECTION
SACE Emax 2 E1.2 E2.2 E4.2 E6.2
Performance levels N/MS N/MS H/MS N/MS H/MS H/MS
Rated uninterrupted current Iu @ 40°C [A] 250 800 800 3200 3200 4000
[A] 630 1000 1000 4000 4000 5000
[A] 800 1250 1250 6300
[A] 1000 1600 1600
[A] 1250 2000 2000
[A] 1600 2500 2500
Neutral pole current-carrying capacity for 4-pole CBs [%Iu] 100 100 100 100 100 50-100
Rated short-time (1s) [kA] 50 66 85 66 85 100
withstand current Icw (3s) [kA] 30 50 66 50 75 1) 100
Rated short-circuit making 400-415 V [kA] 105 145 187 145 187 220
capacity (peak value) Icm
690 V [kA] 105 145 187 145 187 220
Utilization category (according to IEC 60947-3) AC-23A AC-23A AC-23A AC-23A AC-23A AC-23A
Dimensions H - Fixed / Withdrawable [mm] 296/363.5 371/425 371/425 371/425 371/425 371/425
D - Fixed / Withdrawable [mm] 183/271 270/383 270/383 270/383 270/383 270/383
W - Fixed 3p/4p/4p FS [mm] 276/366 384/510 762/888/1014
W - Withdrawable 3p/4p/4p FS [mm] 317/407 425/551 803/929/1069
1) E4.2H/MS 3200A: 66KA Icw (3s)
SACE Emax 2 E1.2 E2.2 E4.2 E6.2
Mechanical life with regular ordinary [Iu] 1000 1600 1600 2000 2500 < 2500 2500 4000 4000 6300
maintenance prescribed by the manufacturer [No. cycles 20 20 25 25 20 20 20 15 12 12
x 1000]
Frequency [Oper./ 60 60 60 60 60 60 60 60 60 60
Hour]
Electrical life with regular 690 V [No. cycles 6.5 6.5 10 8 7 10 8 4 4 2
ordinary maintenance x 1000]
prescribed by the Frequency [Oper./ 30 30 30 30 30 20 20 20 10 10
manufacturer Hour]