AIR CIRCUIT BREAKERS - 1000V
TECHNICAL DATA
OVERVIEW OF THE SACE EMAX FAMILY
Fields of application
E2 E2 E3 E4 E6
Automatic circuit-breakers for E2B/E E2N/E E3H/E E4H/E E6H/E
applications up to 1150V AC
Poles [No.] 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4
Size (40 °C) [A] 1600-2000 1250-1600- 1250-1600- 3200-4000 4000-5000-
2000 2000-2500-3200 6300
Ue [V~] 1150 1150 1150 1150 1150
Icu (1150V) [kA] 20 30 30 (*) 65 65
Ics (1150V) [kA] 20 30 30 (*) 65 65
Icw (1s) [kA] 20 30 30 (*) 65 65
Switch-disconnectors for E2B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MS
applications up to 1150V AC
Poles [No.] 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4
Size (40 °C) [A] 1600-2000 1250-1600- 1250-1600- 3200-4000 4000-5000-
2000 2000 6300
Ue [V~] 1150 1150 1150 1150 1150
Icw (1s) [kA] 20 30 50 65 65
Icm (1000V) [kA] 40 63 105 143 143
AUTOMATIC AIR CIRCUIT BREAKERS 1000V AC - FIXED - 3POLE
In (A) Icu (kA) Icw (1s)
Frame 1000V AC Trip unit Terminal 1000V AC (kA) Part No.
E2N/E 1250 PR121/P LSI H/REAR 30 30 1SDA076322R1
E2N/E 1600 PR121/P-LSI H/REAR 30 30 1SDX047737R1
E2N/E 2000 PR121/P-LSIG H/REAR 30 30 1SDX198660R1
E2N/E 2500 PR121/P-LSIG H/REAR 30 30 1SDX222702R1
- L - I1 (A) = 0.4 - 1 x In; S - I2 (A) = 0.6 - 10 x In; I - I3 (A) = 1.5 - 15 x In
1SDA076322R1 - 4 Pole & other Higher current ratings available. Please contact IPD.
AUTOMATIC AIR CIRCUIT BREAKERS 1000V AC - 3POLE
MOVING PART + CRADLE
In (A) Icu (kA) Icw (1s) Part No. Part No.
Frame 1000V AC Trip unit Terminal 1000V AC (kA) Moving Part Cradle
E2N/E 1250 PR121/P LSI H/REAR 30 30 1SDA076323R1 1SDA059667R1
E2N/E 1600 PR121/P-LSI H/REAR 30 30 1SDX222703R1 1SDA059667R1
E2N/E 2000 PR121/P-LSIG H/REAR 30 30 1SDX222704R1 1SDA059667R1
E2N/E 2500 PR121/P-LSIG H/REAR 30 30 1SDX222705R1 1SDA059669R1
- L - I1 (A) = 0.4 - 1 x In; S - I2 (A) = 0.6 - 10 x In; I - I3 (A) = 1.5 - 15 x In
- 4 Pole & other Higher current ratings available. Please contact IPD.