AIR CIRCUIT BREAKERS
           TECHNICAL CHARACTERISTICS FOR PROTECTION TRIP UNITS - MEASUREMENT FUNCTIONS







          Instantaneous measurements           Parameters                    Precision (Class 1)  1)  Ekip Touch  (*)  Ekip Hi-Touch
          Currents (RMS)              [A]      L1, L2, L3, Ne                0.5%              ●           ●
          Earth fault current (RMS)   [A]      Ig                            2%                ●           ●
          Phase-phase voltage (RMS)   [V]      U12, U23, U31                 0.5%              ●           ●
          Phase-neutral voltage (RMS)  [V]     U1, U2, U3                    0.5%              ●           ●
          Phase sequence                                                                       ●           ●
          Frequency                   [Hz]     f                             0.1%              ●           ●
          Active power                [kW]     P1, P2, P3, Ptot              1%                ●           ●
          Reactive power              [kVAR]   Q1, Q2, Q3, Qtot              2%                ●           ●
          Apparent power              [KVA]    S1, S2, S3, Stot              1%                ●           ●
          Power factor                         total                         2%                ●           ●
          Peak factor                          L1, L2, L3, Ne                                  ●           ●

          Counters recorded from installation or from the last reset Parameters  Precision (Class 1)  1)
          Active energy               [kWh]    Ep total, Ep positive, Ep negative  1%          ●           ●
          Reactive energy             [kVARh]  Eq total, Ep positive, Ep negative  2%          ●           ●
          Apparent energy             [KVAh]   Es total                      1%                ●           ●

          Network Analyzer                     Parameters                    Intervals
                                               - Umin= 0.75...0.95 x Un
                                               - Umax= 1.05...1.25 x Un
                                      [V]
          Hourly average voltage value         - Events counter (nr. of events day by day in the  t = 5...120min  ●  ●
                                      [no]
                                               last year plus the total events in the breaker’s
                                               lifetime)
                                               - Umin= 0.75...0.95 x Un
                                               - Events counter (nr. of events day by day in the
          Short voltage interruptions  [no]                                  t < 40ms          ●           ●
                                               last year plus the total events in the breaker’s
                                               lifetime)
                                               - Umax= 1.05...1.25 x Un
                                               - Events counter (nr. of events day by day in the
          Short voltage spikes        [no]                                   t < 40ms          ●           ●
                                               last year plus the total events in the breaker’s
                                               lifetime)
                                               - Umin1= 0.75...0.95 x Un
                                               - Umin2= 0.75...0.95 x Un
                                               - Umin3= 0.75...0.95 x Un
                                               - Umax1= 1.05...1.25 x Un
          Slow-voltage sags and swells  [no]                                 t = 0.02s...60s   ●           ●
                                               - Umax2= 1.05...1.25 x Un
                                               - Events counter (nr. of events day by day in the
                                               last year plus the total events in the breaker’s
                                               lifetime)
                                               - U neg. seq.=0.02...0.10 x Un
                                      [V]      - Events counter (nr. of events day by day in the
          Voltage unbalance                                                  t = 5...120min    ●           ●
                                      [no]     last year plus the total events in the breaker’s
                                               lifetime)
                                               Current and Voltage
                                               - up to 50o
                                               - Alarm THD: 5...20%
          Harmonic analysis                                                                    ●           ●
                                               - Single harmonic alarm:
                                                 3...10% plus a count of minutes the harmonic
                                                 has been exceeded
          (*) Precision (Class 1) available with dedicated extracode
          With no Class 1, please refer to the precision values below:

          Current (RMS)         1%             Frequency             0.2%           Power factor          2%
          Earth fault current (RMS)  2%        Active power          2%             Active energy         2%
          Phase-phase voltage (RMS)  0.5%      Reactive power        2%             Reactive energy       2%
          Phase-neutral voltage (RMS)  0.5%    Apparent power        2%             Apparent energy       2%

          1)  Class 1 is factory fitted and not available on stock standard breakers. Contact IPD