Page 149 - MCCB-XT2-XT4
P. 149

ABB | SACE Tmax XT

       11 - Ekip Link



                                    Ekip Link is a communication accessory which allows Ekip Touch to be integrated into an internal Ethernet
                                    network with ABB proprietary protocol.
                                    The following functions can be performed with the remote module:
                                     •  Programmable Logic
                                     •  Zone Selectivity
                                    To perform these functions, the system units involved must be equipped with their own Ekip Link and for
                                    each of these, the IP addresses of all the other Ekip Link connected must have been entered.
                                    Each devices is defined as an Actor in the Link network.
                                    Each Ekip Link can interface with up to 15 actors, of which up to 12 for the Zone Selectivity function.
                                    The ports used by the module are:
                                     Port    Service           Notes
                                     18/udp  ABB proprietary   In the case of rapid exchanges of information among ABB devices
                                     319/udp
                                     320/udp  IEEE 1588        Valid with IEEE 1588 protocol enabled
                                     68/udp  DHCP client       DHCP client enabled alternatively as Static address = On


                                    Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Link to Ekip Touch (page
                                    122, 123).
                                    If connected to a withdrawable version of the circuit-breaker, it is possible to detect the racked-in/racked-
                                    out status


                           Network The  Ekip Link modules must be connected to a dedicated network that includes only  Ekip Link and
                                    Ethernet switches for which support for level L2 multicast is declared in the datasheet.
                                    If the network also includes routers, multicast must be enabled and configured in all the level L3 VLAN
                                    interfaces.


                Programmable Logic Activation of up to four bits of the Ekip Link can be programmed via the Programmable Logic function,
                                    each bit according to any combination of the status bits of an actor of which the IP address has been
                                    entered.
                                    These four bits are indicated as Statuses A B C and D; they are remotely programmable and their value is
                                    transmitted to the device to which Ekip Link is connected






































       147 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                        External electronic accessories | 11 - Ekip Link