Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred If several configuration files are present, allows file hierarchy
configuration file between .cid and .iid to be defined .cid
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558 OFF
synchronization signal to be enabled .
(1)
Enables the module to be set up as a master in the the network
IEEE 1558 Master OFF
segment to which it belongs (synchronization clock).
IEEE 1558 Delay Allows the data exchange mode between module and master, either End-to-
mechanism Peer-to-Peer or End-to-End, to be selected. End
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Used to select whether daylight saving time is present (ON) or not OFF
Time (OFF) in the country to which the synchronization time refers
Defines the file loading procedure:
• TFTP always On = port open, loading always possible
TFTP Security • TFTP enable required = port normally closed. To start loading, TFTP
always
level Enable TFTP must be run at the start of the procedure and On
Disable TFTP must be run at the end of the procedure (disable not
necessary, security command).
Defines the limitations to remote opening and closing command
execution:
• Standard commands = standard commands (unrestricted)
CB Open/CB activated Standard
Close command • CB operate request = standard commands not activated. Use commands
programmable functions YC COMMAND and YO COMMAND,
and Request breaker open (28) and Request breaker close (29)
commands
Zone Selectivity Analysis of selectivity input from IEC 61850 module can be enabled/ Disabled
Analysis disabled for each of protections S, S2, G, Gext, D, D(BW), D(FW) (all)
Parameter useful if an IEEE 1588 GrandMaster clock is not available:
• If enabled (ON), the module is seen as an IEEE1588 master clock
by all the slaves/devices in the same local network, even when the
IEEE 1588 source of external synchronism is different from IEEE 1588 (SNTP for OFF
Boundary clock
example)
• If disabled (OFF) the module benefits from the synchronism of the
master in its own network
Enable package Enables the Rate limiter function, which limits the number of
Limitation packages entering the module from the network, to be activated/ Disable
deactivated
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave
IEEE 1558 status or PTP Master Active) or absence (PTP Master but Passive) of a
higher level master
GOOSE Missing Signals that an expected GOOSE has not been received
Configure Mismatch
Decode Error A GOOSE received does not conform to the expected structure
Sequence number error
Remote programmable statuses
(from E to R) Condition (true/false) of the programmable states and information on selectivity
arising from logic defined in the configuration files loaded in module IEC 61850
Zone selectivity remote inputs
146 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 10 - Ekip Com IEC 61850