              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter     Description                                            Default
                                     Preferred     If several configuration files are present, allows file hierarchy
                                     configuration file between .cid and .iid to be defined               .cid
                                                   Allows the IEEE 1588 protocol for distribution of the clock and
                                     Enable IEEE 1558                                                     OFF
                                                   synchronization signal to be enabled .
                                                                                 (1)
                                                   Enables the module to be set up as a master in the the network
                                     IEEE 1558 Master                                                     OFF
                                                   segment to which it belongs (synchronization clock).
                                     IEEE 1558 Delay   Allows the data exchange mode between module and master, either  End-to-
                                     mechanism     Peer-to-Peer or End-to-End, to be selected.            End
                                     Time zone     Defines the time zone to be used for synchronism       +00:00
                                     Daylight Saving   Used to select whether daylight saving time is present (ON) or not   OFF
                                     Time          (OFF) in the country to which the synchronization time refers
                                                   Defines the file loading procedure:
                                                    • TFTP always On = port open, loading always possible
                                     TFTP Security    • TFTP enable required = port normally closed. To start loading,   TFTP
                                                                                                          always
                                     level         Enable TFTP must be run at the start of the procedure and   On
                                                   Disable TFTP must be run at the end of the procedure (disable not
                                                   necessary, security command).
                                                   Defines the limitations to remote opening and closing command
                                                   execution:
                                                    • Standard commands = standard commands (unrestricted)
                                     CB Open/CB    activated                                              Standard
                                     Close command   • CB operate request = standard commands not activated. Use   commands
                                                   programmable functions YC COMMAND and YO COMMAND,
                                                   and Request breaker open (28) and Request breaker close (29)
                                                   commands
                                     Zone Selectivity   Analysis of selectivity input from IEC 61850 module can be enabled/ Disabled
                                     Analysis      disabled for each of protections S, S2, G, Gext, D, D(BW), D(FW)  (all)
                                                   Parameter useful if an IEEE 1588 GrandMaster clock is not available:
                                                    • If enabled (ON), the module is seen as an IEEE1588 master clock
                                                   by all the slaves/devices in the same local network, even when the
                                     IEEE 1588     source of external synchronism is different from IEEE 1588 (SNTP for  OFF
                                     Boundary clock
                                                   example)
                                                    • If disabled (OFF) the module benefits from the synchronism of the
                                                   master in its own network
                                      Enable package   Enables the Rate limiter function, which limits the number of
                                     Limitation    packages entering the module from the network, to be activated/  Disable
                                                   deactivated

                                    (1)  Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time


                Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information               Description
                                     HW and Boot version       General module information
                                     Flash CRC status and result  Information about the correctness of the SW in the module
                                     Ekip Link status          Signals Ethernet cable connection errors
                                     SNTP Server Error         Error in communication with SNTP server
                                     SNTP Server Synchronization  State of synchronism with SNTP server
                                                               Valid with Master IEEE 1588= ON, notifies the presence (Slave
                                     IEEE 1558 status          or PTP Master Active) or absence (PTP Master but Passive) of a
                                                               higher level master
                                     GOOSE Missing             Signals that an expected GOOSE has not been received
                                     Configure Mismatch
                                     Decode Error              A GOOSE received does not conform to the expected structure
                                     Sequence number error
                                     Remote programmable statuses
                                     (from E to R)             Condition (true/false) of the programmable states and information on selectivity
                                                               arising from logic defined in the configuration files loaded in module IEC 61850
                                     Zone selectivity remote inputs