ABB | SACE Tmax XT
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 29).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Defines whether the module has the dynamic (Off) or
Static IP address ON static (On) IP address. OFF
Se = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP
Static Gateway address address of the node to which the module is connected 0.0.0.0
to be selected
Allows the SNTP protocol for distribution of the clock
Enable SNTP client OFF
and synchronization signal to be enabled.
Allows the network server that supplies the SNTP to
SNTP Server Addr. 0.0.0.0
be set.
Defines the write mode of the configuration file in the
module via the TFTP port; two options are available:
• Always ON: the TFTP port is always open and write
Configuration Session is always enabled Always
ON
• Activation requested: the TFTP is opened by a
specific command, which enables write for a limited
time (or for a finite number of data packages)
Write enable command on TFTP port in Activation
Start Configuration ---
mode requested
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the
time of connection to the network in the case of configuration with a
IP address dynamic IP, or can be set via the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which
Network Mask the modules belong and enables modules to be searched for within a
defined set of recipients.
IP address of the node to which the module is connected, in the presence
Gateway address
of several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
MAC address equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
Cfg file Name of the configuration file uploaded to the modules
Cfg file error Code of the error concerning the configuration file (0 = no error)
145 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 10 - Ekip Com IEC 61850