Page 179 - MCCB-XT2-XT4
P. 179
ABB | SACE Tmax XT
Power supply Ekip Com Profinet is supplied directly by the Ekip Touch module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 29).
The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
MAC address equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Defines Dataset (acyclic data) access mode
• each individual acyclic register can be accessed in the Legacy
mode using the Slot, Subslot and Index fields (with Slot fixed at
Data access 3) Legacy
mode
• only complete blocks can be accessed in the Dataset mode; Slot
is fixed at 0, Subslot at 1 and Index defines the block reference
See System Interface for details.
Cyclic data Establishes whether the register of the cyclic data item is Little endian
endianess configured in Big endian or Little endian.
Acyclic data Establishes whether the register of the acyclic data item is Big endian
endianess configured in Big endian or Little endian.
Remote information Certain integrative information concerning the version and state of the module is available via service
connector (via Ekip Connect) or through communication via system bus, i.e.,HW and Boot version, CRC
state (correctness of SW in module), DCP Name, network settings (IP address, Network Mask, Gateway
address)
177 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Internal accessories | 3 - Ekip Com Profinet