Page 184 - MCCB-XT2-XT4
P. 184

ABB | SACE Tmax XT

                       Connections To connect the module to its communication network and for references about the terminals, please
                                    consult circuit diagrams 1SdM000068r0001.
                                    The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
                                    network.
                                    To connect the module to Ekip Touch, please consult document 1SdH002009A1502.


                      Power supply Ekip Com IEC 61850 is supplied directly by the Ekip Touch to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply



            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 29).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:
                                     Parameter          Description                                      Default
                                                        Defines whether the module has the dynamic (Off) or static
                                     Static IP address ON  (On) IP address.                              Off
                                                        Se = On all the associated parameters are enabled
                                     Static address IP   Enables the static IP to be selected            0.0.0.0
                                     address
                                     Static Network Mask  Enables the subnet mask to be selected         0.0.0.0
                                                        When there are several subnets, enables the IP address of the
                                     Static Gateway address                                              0.0.0.0
                                                        node to which the module is connected to be selected
                                                        Allows the SNTP protocol for distribution of the clock and
                                     Enable SNTP client                                                  Off
                                                        synchronization signal to be enabled.
                                     SNTP Server Addr.  Allows the network server that supplies the SNTP to be set.  0.0.0.0
                                                        Defines the write mode of the configuration file in the
                                                        module via the TFTP port; two options are available:
                                                         • Always ON: the TFTP port is always open and write is
                                     Configuration Session  always enabled                               Always ON
                                                         • Activation requested: the TFTP is opened by a specific
                                                        command, which enables write for a limited time (or for a
                                                        finite number of data packages)
                                                        Write enable command on TFTP port in Activation mode
                                     Start Configuration                                                 ---
                                                        requested



                Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Information        Description
                                     SN and version     Identifier and SW version of the module
                                                        Address of the module, assigned to the module by a DHCP server at the
                                                        time of connection to the network in the case of configuration with a
                                     IP address         dynamic IP, or can be set via the menu in the event of a static IP
                                                             NOTE: without a DHCP server, the module automatically adopts a
                                                            random IP address within the 169.254.xxx.xxx range
                                                        Subnet mask; identifies the method for recognizing the subnet to which
                                     Network Mask       the modules belong and enables modules to be searched for within a
                                                        defined set of recipients.
                                                        IP address of the node to which the module is connected, in the presence
                                     Gateway address
                                                        of several subnets
                                                        Address assigned by ABB, with OUI (Organizationally Unique Identifier)
                                     MAC address        equal to ac:d3:64, which uniquely identifies the manufacturer of an
                                                        Ethernet device
                                     Cfg file           Name of the configuration file uploaded to the modules
                                     Cfg file error     Code of the error concerning the configuration file (0 = no error)





       182 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                         Internal accessories | 5 - Ekip Com IEC 61850
   179   180   181   182   183   184   185   186   187   188   189