Page 180 - MCCB-XT2-XT4
P. 180
ABB | SACE Tmax XT
4 - Ekip Com EtherNet/IP TM
Ekip Com EtherNet/IP is a communication accessory which allows Ekip Touch to be integrated into an
TM
Ethernet network with EtherNet/IPTM communication protocol, with supervision functions
The module is configured as master and remotely, you can:
• read Ekip Touch measurements and information
• manage certain controls, including opening and closing the actuator (MOE-E)
• access information and parameters not available on the display
NOTE: the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 121).
Depending on the parameter settings, described in the next pages, the ports used by the module are:
Port Description Default
Encapsulation Protocol (example: ListIdentity, UCMM, CIP Transport
44818 TCP
Class 3)
44818 UDP 44818 UDP Encapsulation Protocol (example: ListIdentity)
2222 UDP 2222 UDP CIP Transport Class 0 or 1
68/UDP DHCP Client Client DHCP enabled as an alternative to Static address = On
IMPORTANT: each circuit-breaker can house one module only; configuration with external
communication modules is not allowed if an internal module is present.
Safety and cyber security Since the module allows the actuator connected to Ekip Touch and access to the data in the unit to be
checked, it can only be connected to networks equipped with all the necessary security and prevention
measures against unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the case
may be). The plant manager must establish and maintain appropriate measures (such as
but not limited to the installation of firewalls, application of authentication measures,
encryption of data, installation of antivirus programs, etc.) to protect the product,
the network, the customer system and interface against any kind of security breaches,
unauthorized access, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security
breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or
information.
• The module cannot be connected directly to the Internet. Only connect to dedicated
Ethernet networks with EtherNet/IP communication protocol
TM
TM
Characteristics Ekip Com EtherNet/IP integrates the following characteristics:
• Integrated status contacts (Open/Close and Trip)
• Buffer battery to maintain the Date/Time in the absence of auxiliary power supply.
NOTE: to replace the buffer battery, please consult document 1SdH001000r0509
Connections To connect the module to its communication network and for references about the terminals, please
consult circuit diagrams 1SdM000068r0001.
The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
network.
To connect the module to Ekip Touch, please consult document 1SdH002009A1502.
178 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Internal accessories | 4 - Ekip Com EtherNet/IP TM