Parameters 2 The Datalogger 1 and Datalogger 2 submenus (available if the number of dataloggers selected is: 2)
contain the following options:
Parameter Description Default
Trigger event at which the recording is to be interrupted; the
main protection options (trips, timings, alarms) and the actuator
Stop Event None
status (open/closed) are displayed.
The Custom option can be configured via Ekip Connect
Recording interruption delay, calculated from the trigger; the
Stop delay value is given in seconds and can be set within a range: 0 s to 10 0.01 s
s, in 0.01 s steps
Restart Recording start command
Stop Manual recording stop command
Memory Type
Ekip Connect enables the Memory Type (Non volatile/Volatile) to be selected:
• Non volatile: Ekip Touch maintains the registration even when off; the life of the internal battery
of the unit can be sensibly less than the declared value in the absence of auxiliary power supply.
• Volatile: Ekip Touch loses the recording if it is switched off; when the unit is switched on again,
the datalogger automatically restarts, losing the previously stored data.
The parameter is configured by default as Non volatile.
Signallings If there is a recording present, Ekip Touch provides the information on the diagnosis bar (DLog1 available).
NOTE: In the configuration with two dataloggers, the specific indication of the available
recording is shown (DLog1 available or DLog2 available)
Ekip Connect Ekip Connect 3 has two specific areas for the Datalogger function:
• Datalogger for configuring the recording parameters with a user-friendly interface, and for
downloading the recordings
• Data Viewer for opening and consulting the recordings
Both areas are available in the Tools menu of Ekip Connect.