All the thresholds are given as a percentage of rated voltage Un and can be set from 10% to 95% Un, in
5% steps.
All the times are given in seconds and can be set within the range: 0.04 s to 60 s, in variable steps
Parameter Description Default
V sag Th Short Control threshold of Sags Short counter 10 % Un
Minimum duration of sag below the Short threshold to validate
V sag dur Short 0,8 s
the count of the Sags Short counter
V sag Th
Middle Control threshold of Sags Middle counter 45 % Un
V sag dur Minimum duration of sag below the Middle threshold to validate
Middle the count of the Sags Middle counter 0,8 s
V sag Th Long Control threshold of Sags Long counter 95 % Un
Minimum duration of sag below the Long threshold to validate
V sag dur Long 0,8 s
the count of the Sags Long counter
NOTE: Ekip Touch accepts changes to the parameters subject to compliance with the
following limitations: V sag dur Long ≥ V sag dur Middle ≥ V sag dur Short
Swells Menu (Swell)
All the thresholds are given as a percentage of rated voltage Un and can be set from 105% to 125% Un, in
5% steps.
All the times are given in seconds and can be set within the range: 0.04 s to 60 s, in variable steps
Parameter Description Default
V swell Th Control threshold of the Swell Short counter 125 % Un
Short
V swell dur Minimum duration of swell above the Short threshold to validate 0,8 s
Short the count of the Swell Short counter
V swell Th Long Control threshold of the Swells Long counter 105 % Un
V swell dur Minimum duration of swell above the Long threshold to validate
Long the count of the Swells Long counter 0,8 s
NOTE: Ekip Touch accepts changes to the parameters subject to compliance with the
following limitations: V sag dur Long ≥ V sag dur Middle ≥ V sag dur Short
Harmonics (Current and Voltage)
All the thresholds are given as a percentage and can be set within the range: 5% to 20% (total THD) or: 3%
to 10% (single harmonics) in 1% steps.
Menu Parameter Description Default
THD Control threshold of the THD Voltages counter 5 %
Threshold
Current
Single Control threshold of the single harmonics counters of 5 %
harmonic th the voltages
THD Control threshold of the THD Current counter 5 %
Threshold
Voltage
Single Control threshold of the single harmonics counters of 5 %
harmonic th the currents
111 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Ekip Touch - Measurements | 5 - Network Analyzer