Page 117 - MCCB-XT5
P. 117

Continued from the previous page                               ABB | SACE Tmax XT
                                     Counters (Sags
                                     Middle)            Description
                                     Last time stamp    Date and time of last recording of the Sags Middle counter
                                     Sags Middle        Value of last sag below the Sags  Middle [V] threshold
                                     Sags Long          Duration of last sag below the Sags  Middle [ms] threshold
                                     Actual number of S.  Sags Middle count of the current day
                                     Actual [day -2 ... day -7]  Sags Middle count of the last seven days of activity, calculated using the
                                     number of S.       internal clock of the unit
                                     Counters (Sags     Description
                                     Middle)
                                     Last time stamp    Date and time of last recording of the Sags Long counter
                                     Sags Middle        Value of last sag below the Sags  Long[V] threshold
                                     Sags Long          Duration of last sag below the Sags  Long[ms] threshold
                                     Actual number of S.  Sags Long count of the current day
                                     Actual [day -2 ... day -7]  Sags Long count of the last seven days of activity, calculated using the
                                     number of S.       internal clock of the unit




                             Swells Certain counters relating to swells are available in the  Counters -  Day -1 and Counters -  Cumulative
                                    submenus:
                                     Counters (Sags
                                     Middle)            Description
                                                        Counts the number of times that any line-to-line voltage exceeds the V
                                     Swells Short
                                                        swell Th Short threshold for longer than V swell dur Short
                                                        Counts the number of times that any line-to-line voltage exceeds the V
                                     Swells Long
                                                        swell Th Long threshold for longer than V swell dur Long

                                    The count refers to the reference menu interval (previous day or cumulative)
                                           NOTE: since an event may fall under more than one category, only the counter of the main
                                           type (long > short) is increased

                                    Additional List
                                     Counters (Swells
                                     Short)             Description
                                     Last time stamp    Date and time of last recording of the Swells Short counter
                                     Last value         Value of last swell above Swells Short [V] threshold
                                     Last duration      Duration of last swell above Swells Short [ms] threshold
                                     Actual number of S.  Swells Short count for the current day
                                     Actual [day -2 ... day -7]  Swells Short count of the last seven days of activity, calculated using the
                                     number of S.       internal clock of the unit
                                     Counters (Swells   Description
                                     Long)
                                     Last time stamp    Date and time of last recording of the Swells Long counter
                                     Last value         Value of last swell above Swells Long[V] threshold
                                     Last duration      Duration of last swell above Spikes[ms] threshold
                                     Actual number of S.  Swells Long count for the current day
                                     Actual [day -2 ... day -7]  Swells Long count of the last seven days of activity, calculated using the
                                     number of S.       internal clock of the unit

















       115 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                     Ekip Touch - Measurements | 5 - Network Analyzer
   112   113   114   115   116   117   118   119   120   121   122