       2 - Additional settings



                       Presentation Via the service connector (via Ekip Connect) or system bus communication, you can:
                                    A description of the different functions is given below.


               Programmable States There are sixteen independent programmable states identified by the letters A, B, C, D, E, F, G, H, I, L, M, N,
                                    O, P, Q, R, offering different solutions for event control.
                                    Each programmable status can have two values: True or False. There are also various configuration
                                    parameters available:
                                     •  Trigger: event or combination of several status activation events (up to 24, in AND or OR logic
                                       configuration).
                                     •  On Delay: status activation delay calculated from trigger presence onwards.
                                     •  Off Delay: status de-activation delay calculated from trigger absence onwards.
                                           NOTE: the status activates if the trigger is present for longer than the On delay setting and
                                           de-activates if the trigger is absent for longer than the Off delay setting





























                                    Figure 38
                                    The statuses can be used with external module Ekip Signalling 10K, on Link Bus or with the programmable
                                    functions, so as to convey the required signaling combination to the contacts.


                             Filters A measuring filter (V0 filter) can be activated with V0 external neutral connection
                                    If the filter is activated, the measurements and specific protections of V0 are dealt with differently: Ekip
                                    Touch applies a pass-band filter to the signal so as to measure the fundamental component only (50 or
                                    60 Hz).


               TAG Name, User data Tags that can be programmed by the user to facilitate remote identification of units.
                                           NOTE: the Name TAG and communication address form the identification used by Ekip
                                           Connect for the connected devices


















       122 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                        Ekip Touch - Settings | 2 - Additional settings