Page 121 - MCCB-XT5
P. 121
ABB | SACE Tmax XT
Configuration The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be
activated, is available for the 3P CB (page 206).
Activation of the configuration with External neutral (3P + N) enables:
• histograms of phase Ne in the Histograms page
• neutral current measurements
• submenu for configuring the Neutral protection (Neutral Protection)
• neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Line frequency Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
60 Hz.
NOTE: the measurements are taken on the basis of the set grid frequency: incorrect
configuration of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.
Modules The Modules menu provides various options:
Parameter Description Default
The parameter defines the mode in which the parameters are
written in the unit:
• Local: parameter editing only via the display or service
connector
• Remote: parameter editing only remotely (Ekip Com modules)
Local/Remote NOTES: Local
• the Remote mode requires the presence of auxiliary
power supply and Ekip Com modules, otherwise it disables
automatically
• However, the Local/Remote parameter can still be edited
in the Remote mode
The parameter enables communication between the Trip unit
and modules installed via terminal box or outside the unit to be
activated.
Correct communication between unit and modules is confirmed
by:
Local bus Off
• population of the Modules menu with all the modules
connected
• Power Leds of the modules on and synchronized like the power
led of Ekip Touch
• absence of Local Bus alarm in the diagnosis bar
Ekip Signalling 1K Menu with the parameters of the module (page 200)
Menu with the parameters of the module Measurement (page
Ekip Measuring
128)
- Menu of every module connected and detected (from page 132)
Access to the LOCAL Switch On and RESET signaling functions
Functions
(from page 78)
119 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Ekip Touch - Settings | 1 - Main settings