Page 122 - MCCB-XT5
P. 122

ABB | SACE Tmax XT

                           Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby
                                    limiting the possibility of configuring all the options on the display (in the Local mode) or via modules
                                    Ekip Com (in the Remote mode).
                                    Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
                                    unauthorized persons to be increased.
                                           NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
                                           enabled)
                                    Ekip Touch is supplied with the parameter set to: On.


                            System The System menu provides various options:
                                     Parameter    Description                                         Default
                                     Date         Setting the current date
                                     Time         Setting the current time
                                     Language     Setting the language in display menus               English
                                     PIN          PIN setting (page 39)                               00001

                                           IMPORTANT: setting and checking Date and Time is important for all the recording
                                           functions (trips or measurements); in the event of date and time glitches, reset and if
                                           necessary replace the battery inside Ekip Touch (page 19).



                              View The View menu provides various options:
                                     Parameter    Description                                             Default
                                                  Enables the orientation of the Alarms List, Measuring Instruments
                                     TFT orientation and Main Measurements pages to be set. The options are: Horizontal,   Horizontal
                                                  Vertical clockwise, Vertical counter-clockwise
                                                  Allows you to activate a supplementary information page, which can
                                                  be accessed by pressing the iTEST button twice from any page with a
                                     Customer page                                                        Off
                                                  diagnosis bar. The information on the new page can be configured via
                                                  Ekip Connect (page 123)
                                                  Allows the current to be displayed in the Measuring instruments page
                                     Ammeter
                                     Phase        to be set from among the following options: Imax, I1, I2, I3, Ne (only in   Imax
                                                  the 4P or 3P + N configuration)
                                     Voltmeter    Allows the voltage to be displayed in the Measuring instruments page   Vmax
                                     Phase        to be set from among the following options: Vmax, V12, V23, V31




                       Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 103).
                                    Ekip Touch is supplied with the parameter set to: On.































       120 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                            Ekip Touch - Settings | 1 - Main settings