Page 122 - MCCB-XT5
P. 122
ABB | SACE Tmax XT
Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby
limiting the possibility of configuring all the options on the display (in the Local mode) or via modules
Ekip Com (in the Remote mode).
Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
unauthorized persons to be increased.
NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
Ekip Touch is supplied with the parameter set to: On.
System The System menu provides various options:
Parameter Description Default
Date Setting the current date
Time Setting the current time
Language Setting the language in display menus English
PIN PIN setting (page 39) 00001
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset and if
necessary replace the battery inside Ekip Touch (page 19).
View The View menu provides various options:
Parameter Description Default
Enables the orientation of the Alarms List, Measuring Instruments
TFT orientation and Main Measurements pages to be set. The options are: Horizontal, Horizontal
Vertical clockwise, Vertical counter-clockwise
Allows you to activate a supplementary information page, which can
be accessed by pressing the iTEST button twice from any page with a
Customer page Off
diagnosis bar. The information on the new page can be configured via
Ekip Connect (page 123)
Allows the current to be displayed in the Measuring instruments page
Ammeter
Phase to be set from among the following options: Imax, I1, I2, I3, Ne (only in Imax
the 4P or 3P + N configuration)
Voltmeter Allows the voltage to be displayed in the Measuring instruments page Vmax
Phase to be set from among the following options: Vmax, V12, V23, V31
Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 103).
Ekip Touch is supplied with the parameter set to: On.
120 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Ekip Touch - Settings | 1 - Main settings