ABB | SACE Tmax XT
Summary page Press on the sides of the display (1) from the Home page to access further summary pages for certain
measurements:
• Main measurements page: maximum phase current, maximum line-to-line voltage, power factor,
total active/reactive/apparent powers
• Ekip Synchrocheck main measurements page (when module is present): Int and Ext frequencies
and voltages, phase difference, synchronism status (page 34)
Figure 16
NOTE: both pages can be set as the main page by pressing HOME, holding it for five
seconds and confirming the message on the display
Measuring instruments
Figure 17
Depending on the Trip unit model, certain measurements acquired in real time are shown on these pages
by means of a pointer; each page displays a specific measurement:
Page Measurement type page Unit of measurement/indicator
1 Maximum phase current A
2 Maximum line-to-line voltage V
3 Total active power kW
4 Total reactive power kVAR
5 Total apparent power kVA
The scale of values ranges from 0 to 125 % and refers to the rated values set (for powers: rated current x
rated voltage x √3).
Press on the sides of the display to browse the pages; quit the Measurement tools section with the HOME
key.
Page orientation (horizontal by default) can be changed in the Settings menu (page 120).
NOTE: each page can be set as the main page by pressing HOME, holding it for five seconds
and confirming the message on the display