Page 32 - MCCB-XT5
P. 32

ABB | SACE Tmax XT

                     Measurements














                                    Figure 18

                                    If provided for by Trip unit model, the Measurements pages contain a list of measurements acquired in
                                    real time, expressed in absolute value:
                                     Page    Name               Measurements
                                     1      Current             Currents: phase, earth fault
                                     2      Voltage             Voltages: line-to-line, phase, neutral
                                     3      Active power        Phase and total active powers
                                     4      Reactive power      Phase and total reactive powers
                                     5      Apparent power      Phase and total apparent powers
                                     6      Energy counters     Total active, reactive and apparent energies
                                                                Summary of Ekip Signalling 3T module measurements, if
                                     9      Ekip Signalling 3T
                                                                installed

                                    Ekip Touch configuration involves certain exceptions:
                                     •  the Ne current measurements are available with 4P and 3P + N configurations
                                     •  the phase voltage measurements are available with the 4P and 3P + active external neutral voltage
                                       configuration
                                     •  with the 3P configuration, pages: Active Power, Reactive Power and Apparent Power are replaced
                                       by the Powers page with the total active, reactive and apparent power measurements
                                    Press the sides of the display to browse the pages; press the HOME key to quit.
                                           NOTE: each page can be set as the main page by pressing HOME, holding it for five seconds
                                           and confirming the message on the display











































       30 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                    Ekip Touch - Interface and menus | 3 - Graphic pages