LEDs LEDs Colour Description
Indicates the on status of Ekip Touch:
• off: no power and unit off
• on, steady (Power mode) or flashing (Alive mode): unit on and self-supplied
Power by external Vaux or service connector
Green The Power mode or Alive mode can be selected via Ekip Connect: if the Alive
mode has been selected and external modules are connected, the Power leds
of Ekip Touch and the modules flash in the synchronized mode.
More details are given in the chapter on Ekip Connect additional functions on
page 123
Signals that certain alarms are present:
Warnings • off: no alarm
Yellow • on steady: prealarm of an active protection or status contacts error
• two flast flashes every 0.5 s: trip unit parameter configuration error
• fast flash: Rating Plug or Measurement module installation error
Signals that an alarm is present:
• off: no alarm
Alarm • on steady: on steady signals a TRIP due to a protection
Red
• two flast flashes every 2 seconds: Rating Plug error
• on with fast flashing: protection timing tripped or alarm due to
disconnection of a current sensor
If on and flashing at the same time, the Warning and Alarm leds signal an alarm caused by a hardware
error inside the Trip unit.
This case requires assistance from ABB.
Push-buttons Push-
button Description
Allows different areas of the menu to be accessed:
HOME • from pages: HOME, Histograms, Measuring instruments, Measurements, Main
measurements -> open: Main page
• from pages: Main page, Alarm list, at any point of the menu area -> open: HOME
page
Allows certain pages of information about the unit to be rapidly consulted; press the
button in successionj to display the following pages:
• Alarm list, if messages are present
• Info, if Customer Page option is active (page 123)
• Protection unit, with information about Ekip Touch
iTest • Circuit breaker, with information about the CB
• Last trip, with information about the last trip, if available
Consultation is active from pages: HOME, Histograms, Measuring instruments,
Measurements, Main measurements
NOTE: with Ekip Touch off and the internal battery charged, press iTEST to
temporarily switch on the Power led and, in the case of a trip, the display with
information about the trip protection and the Alarm led
Service connector The service connector enables Ekip Touch to be connected to Ekip TT, Ekip T&P and Ekip Programming,
allowing the unit to be temporarily supplied, parameter configuration prior to putting into service, tests
and extension of the configuration functions.
IMPORTANT: only use cables supplied by ABB or with ABB accessories
25 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Ekip Touch - Interface and menus | 1 - Presentation of interface