Page 49 - MCCB-XT5
P. 49

Continued from the previous page                               ABB | SACE Tmax XT
                                    Ekip M Touch
                                    With Ekip M Touch, G protection features the following differences compared to the other models:
                                     •  Block BlockOnStartup enabled and non-editable (page 76)
                                     •  StartUp Time non-editable and set with the Motor start-up value, depending on the trip class
                                       (page 121)
                                     •  curve set as t=k, non-editable
                                    Limitations and additional functions
                                     •  in the presence of curve t= k/I , the protection trip time is forced to t4 if the calculation results
                                                                2
                                       give a theoretical value lower than t4 itself
                                     •  in the absence of Vaux, the minimum threshold is 0.25 In (for In = 300 A) or 0.2 In (for all the other
                                       sizes); if lower values are set, the Trip unit forces the threshold to the minimum admissible value
                                       and the "Configuration" error appears
                                     •  depending on the I4 threshold setting, the protection deactivates for an Ig higher than: 8 In with
                                       threshold I4 ≥ 0.8 In; 6 In with 0.8 In > I4 ≥ 0.5 In; 4 In with 0,5 In > I4 ≥ 0,2 In; 2 In with I4 > 0.2 In
                                     •  operation with t4 = instantaneous requires the presence of Vaux; in self-supply, the Trip unit forces
                                       the time to 100 ms and the "Configuration" error appears
                                     •  the block functions and type of selectivity can also be accessed by means of the service connector
                                       (via Ekip Connect) or communication via system bus (page 73)
                                     •  with CB in UL standard configuration, the maximum value of t4 is 400 ms


                    Protection MCR Function
                                    The protection remains activated for a time interval running from the open - closed change of status of
                  t                 the CB, after which it deactivates.
                       I3     MCR
                                    If, during this time interval, the current of one or more phases exceeds threshold I3, the protection
                                    transmits the TRIP command after a non-programmable fixed time.
                                    The MCR protection only functions with Vaux.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                  I  •  summary table of the protections with the operating characteristics (page 81)
                                     •  the graph with trip curve (page 89)
                                           NOTE: to activate MCR, protection I must be disabled
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu.
                                                  Establishes the value that activates the protection.
                                     Threshold I3  The value is given as both absolute value (A) and relative value (In)  6 In
                                                  and can be set within the range: 1.5 In to 10 In, in 0.1 In steps
                                                  Defines the time interval in which the MCR protection remains
                                                  activated, as calculated from the open - closed change of status
                                     Monitor Time                                                     0,04 s
                                                  The value is given in seconds and can be set within the range:
                                                  0.04 s to 0.5 s, in 0.01 s steps
                                                  Activates/deactivates the function
                                                       NOTE: if at least two of the selectivity S, S2, I, 2I and MCR
                                     ZoneSelectivity  are enabled, the input and output are shared with the OR   OFF
                                                     function; it is sufficient that even a selectivity is activated to
                                                     stimulate inputs and outputs

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or
                                    communication via system bus (page 73)




















       47 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                               Protections | 2 - Standard Protections