Page 54 - MCCB-XT5
P. 54

ABB | SACE Tmax XT

                      OV Protection Function
                                    The protection sends a TRIP command if one or more line-to-line voltages detected by the unit exceed
                  t                 threshold U9 for longer than t9.
                       U9     OV    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 82)
                                     •  the graph with trip curve (page 92)
                             t9
                                    Parameters
                                 V   Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the
                                     Enable                                                             OFF
                                                parameters menu
                                                Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                information
                                                Establishes the value that activates the protection.
                                     Threshold
                                     U9         The value is given as both absolute value (Volts) and relative value (Un)  1,05 Un
                                                and can be set within the range:  1 Un to 1.5 Un in 0.001 Un steps
                                                This is the trip time of the protection; the value is given in seconds
                                     Time t9                                                            5 s
                                                and can be set within a range: 0.05 s to 120 s, in 0.01 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 73).



                     UV2 Protection Function
                                    UV2 protection functions in the same way as UV protection: the protection sends a TRIP command if one
                  t                 or more line-to-line voltages detected by the unit drop below threshold U15 for longer than t15.
                              UV2
                       U15          It is independent of UV protection, thus thresholds and functions of the two protections can be
                                    programmed so as to take advantage of different plant solutions (example: signaling with UV and open
                    t15             command with UV2 or vice versa, or both for signaling or tripping).
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                 v   •  summary table of the protections with the operating characteristics (page 82)
                                     •  the graph with trip curve (page 91)
                                    Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the
                                     Enable                                                             OFF
                                                parameters menu
                                                Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                information
                                                Establishes the value that activates the protection.
                                     Threshold   Value is given as both absolute value (Volts) and relative value (Un) and  0,9 Un
                                     U15
                                                can be set within range:  0.05 Un to 1 Un in 0.001 Un steps
                                                This is the trip time of the protection; the value is given in seconds
                                     Time t15                                                           5 s
                                                and can be set within a range: 0.05 s to 120 s, in 0.01 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 73).