ABB | SACE Tmax XT

       3 - Voltage protections



                               List The Voltage protections, available by default for the Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch and Ekip
                                    M Touch models and configurable in the remaining models as additional SW package, are:
                                     Name                      Type of protection        Page
                                     UV                        Minimum voltage           51
                                     OV                        Maximum voltage           52
                                     UV2  (1)                  Minimum voltage           52
                                     OV2  (1)                  Maximum voltage           53
                                     Phase Sequence            Phase sequence error      53
                                     VU                        Voltage unbalance         53

                                    (1)  protections UV2 and OV2 are not available by default with Ekip G Touch. However, they can be
                                    integrated by requesting the relative SW package

                      UV Protection Function
                                    The protection sends a TRIP command if one or more line-to-line voltages detected by the unit drop
                  t                 below threshold U8 for longer than t8.
                              UV
                         U8         To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 82)
                     t8              •  the graph with trip curve (page 91)
                                    Parameters
                                 v   Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the
                                     Enable                                                             OFF
                                                parameters menu
                                                Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                information
                                                Establishes the value that activates the protection.
                                     Threshold
                                     U8         Value is given as both absolute value (Volts) and relative value (Un) and  0,9 Un
                                                can be set within range: 0.05 Un to 1 Un in 0.001 Un steps
                                                This is the trip time of the protection; the value is given in seconds
                                     Time t8                                                            5 s
                                                and can be set within a range: 0.05 s to 120 s, in 0.01 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).


































       51 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                Protections | 3 - Voltage protections