       5 - Frequency protections



                               List The Frequency protections, available by default for the Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch and
                                    Ekip M Touch models and configurable in the remaining models as additional SW package, are:
                                     Name                      Type of protection        Page
                                     UF                        Minimum frequency         58
                                     OF                        Maximum frequency         59
                                     UF2  (1)                  Minimum frequency         59
                                     OF2  (1)                  Maximum frequency         60

                                    (1)  protections UF2 and OF2 are not available by default with Ekip G Touch. However, they can be
                                    integrated by requesting the relative SW package


                      UF Protection Function
                                    The protection sends a TRIP command if the grid frequency read by the unit drops below threshold f12
                  t                 for longer than t12.
                              UF
                        f12         The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                    t12              •  summary table of the protections with the operating characteristics (page 82)
                                     •  the graph with trip curve (page 94)
                                 f  Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (Hertz) and relative
                                     Threshold f12                                                    0,9 Fn
                                                  value (Fn) and can be set within the range: 0.9 Fn to 1 Fn in 0.001
                                                  Fn steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t12     seconds and can be set within a range: 0.06 s to 300 s, in 0.01 s   3 s
                                                  steps


                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).

































       58 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                              Protections | 5 - Frequency protections