Page 58 - MCCB-XT5
P. 58

Continued from the previous page                               ABB | SACE Tmax XT
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                     Curve        Allows the operating mode, Step or Lin, to be selected  Scal
                                                  Establishes the value that activates the protection and
                                                  contributes towards calculating the trip time.
                                     Threshold I21  The value is given as both absolute value (amperes) and relative   1 In
                                                  value (In) and can be set within the range: 0.6 In to 10 In, in 0.1 In
                                                  steps
                                                  It is the voltage that determines the change in trip threshold I21;
                                                  the behavior differs, depending on the mode selected  (1)
                                     Threshold Ul2  The value is given as both absolute value (V) and relative value   1 Un
                                                  (Un) and can be set within the range: 0.2 Un to 1 Un in 0.01 Un
                                                  steps
                                                  The parameter is shown by the Lin curve and contributes towards
                                                  I21 trip threshold calculation:
                                                   • with voltage reading < Uh2 (and ≥ Ul2), the threshold changes
                                                  gradually  (1)
                                     Threshold Uh2                                                    1 Un
                                                   • with voltage reading ≥ Uh2, the threshold is I21
                                                  The value is given as both absolute value (V) and relative value
                                                  (Un) and can be set within the range: 0.2 Un to 1 Un in 0.01 Un
                                                  steps
                                                  I21 threshold calculation constant.
                                     Threshold Ks2  The value is given as percentage of threshold I21 and can be set   0,6 I21
                                                  within the range: 0.1 I21 to 1 I21, in 0.01 steps
                                                  This is the trip time of the protection.
                                     Time t21     The value is given in seconds and can be set within the range:   0.1 s
                                                  0.05 s to 30 s, in 0.01 s steps

                                    (1) Trip threshold (depending on the operating curve)
                                     Mode     Voltage reading     Trip threshold
                                              < UI2               Ks2 x I21
                                     Scal
                                              ≥ UI2               I21
                                              < UIs               Ks2 x I21
                                     Lin
                                              ≥ Ul2 (e < Uh2)     ((I21 x ( 1 - Ks2 ) x ( U   - Uh2 ) ) / (Uh2 - Ul2) ) + I21
                                                                                   mis
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 76).































       56 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                        Protections | 4 - Voltage Advanced protections