Continued from the previous page                               ABB | SACE Tmax XT
                                     Parameter   Description                                              Default
                                     StartUp     Activates/deactivates the function and availability of the associated   OFF
                                     enable      parameters on the display
                                                 Protection threshold valid during Startup time, in the conditions in
                                     StartUp                                                         (2)
                                     Threshold   which the function is activated and with forward current direction .  2 In
                                     Fw  (2)     The value is given as both absolute value (amperes) and relative value
                                                 (In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                 Protection threshold valid during Startup time, in the conditions in
                                     StartUp     which the function is activated and with backward current direction.
                                     Threshold   The value is given as both absolute value (amperes) and relative value   2 In
                                     Bw  (2)
                                                 (In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                 This is the time for which the StartUp threshold remains activated and
                                     StartUp Time    is calculated from the moment the activation Threshold is exceeded
                                     (2)         The value is given in seconds and can be set within the range: 0.1 s to   0.1 s
                                                 30 s, in 0.01 s steps
                                                 Ekip Touch calculates the phase displacement angle between active
                                                 and apparent power measured: when phase displacement exceeds
                                     Direction Min
                                     Angle       the set Direction Min Angle parameter, the unit considers the fault   3,6 °
                                                 direction to have been identified. The value is given in degrees and can
                                                 be set within a range of 15 values from 3.6° to 69.6°

                                    (1)  details on page 74
                                    (2)  details on page 76

                                    Limitations and additional functions
                                    the functions blocking the type of selectivity and the Trip only Forward and Trip Only Backward parameters
                                    can also be accessed by means of the service connector (via Ekip Connect) or communication via system
                                    bus (page 76).
                                    Notes
                                     •  activation of D directional protection automatically activates the alarm that monitors phase
                                       sequence (which can also be excluded and activated in the manual mode): note how, in the case
                                       of a cyclic sequence of phases that differs from the set value, in the event of a fault the directional
                                       protection inverts the reference direction with respect to the expected direction; details of the
                                       phase sequence protection are available on page 53
                                     •  in the case of small overcurrents, the behavior of the directional protection is influenced by the
                                       type of load: to prevent the direction of the fault current from being incorrectly interpreted in the
                                       case of capacitive loads, it is advisable for the setting of that protection to be made on the basis
                                       of real fault conditions and not overloads








































       63 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                 Protections | 6 - Power protections