P. 85

ABB | SACE Tmax XT

                  ROCOF Protection   Protection                  Trip threshold
                                     [ANSI code]   Trip time t  t  tolerance  (3)  Trip time tolerance
                                     ROCOF [81R]   t  = t28      ± 10 %  (6)    the best between ± 20% and 200 ms
                                                     t


                  Motor protections  Protection                  Trip threshold
                                     [ANSI code]   Trip time t  t  tolerance  (3)  Trip time tolerance
                                     R JAM [51LR]  t  = tj       ± 10 %         with If ≤ 6 In: ± 7 % / with If > 6 In: ± 10 %
                                                     t
                                     R STALL [51LR]  t  = ts     ± 10 %         ± 10 %
                                                     t
                                     UC [37]       t  = tuc      ± 15 %         ± 20 %
                                                     t
                                     U             t  = tu  (8)  ± 15 %         ± 20 %
                                                     t

                Note on protections  (1)  use trip and threshold current values expressed in In for calculating t  (example: If = 0.8 In, I1= 0.6
                                                                                            t
                                    In)
                                    (2)  with t4 = instantaneous, the maximum tolerance is 50 ms
                                    (3)  Tolerance values valid with Trip unit at steady state or on with auxiliary power supply, trip time ≥
                                    100 ms, temperature and signals within operating limits; the tolerances in the table after the notes
                                    are applicable if the conditions are not guaranteed
                                    (4)  the trip unit considers 3% hysteresis for quitting alarm condition
                                    (5)  tolerance valid for frequencies within range: fn ± 2 %. A ± 5% tolerance is applicable for off range
                                    frequencies
                                    (6)  ± 20% for threshold 0.4 Hz / s
                                    (7)  time to be considered valid after Motor start-up
                                    (8)  time to be considered valid with protection in alarm status after Motor start-up; if the alarm
                                    appears during Motor start-up, the trip unit calculates and uses the lowest value between tu and the
                                    half of Motor start-up
                                    (10)  with If ≥ 18 kA, t  ≤ 3 ms;
                                                    t
                                        with If < 18 kA and If ≥ I31 * 3, t  ≤ 7 ms (If three-phase) or t  ≤ 9 ms (If single-phase);
                                                                                     t
                                                               t
                                        with If < 18 kA and If < I31 * 3, t  ≤ 15 ms.
                                                               t
                                        (operating parameters guaranteed with Vaux auxiliary power supply)
                                    (11)  tolerance valid with threshold U14 > 10%; with U14 ≤ 10% (and >6%), the tolerance is 10%; with
                                    U14 < 5%, the tolerance is 15%
                                    Performance guaranteed in all operating conditions
                                     Protection     Trip threshold tolerance        Trip time tolerance
                                                    Activation within range: (1.05 to 1.2)
                                     L                                              ± 20 %
                                                    x I1
                                     S              ± 10 %                          ± 20 %
                                     I / 2I         ± 15 %                          ≤ 60 ms
                                                                                    ± 20 % (60 ms with t4 =
                                     G              ± 15 %
                                                                                    instantaneous)
                                     UF / UF2 / OF /   ± 2 %                        ± 20 %
                                     OF2
                                                                                    ± 20 %; in the case of single-phase
                                     RV             ± 10 %                          self-supply: the highest between ± 20
                                                                                    % and 30 ms
                                     Other          --                              ± 20 %





















       83 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                Protections | 12 - Performance table