Page 81 - MCCB-XT5
P. 81

ABB | SACE Tmax XT

       11 - Logic selectivity



                       Presentation Zone Selectivity via Link Bus is indicated as Logic Selectivity.
                                    Logic Selectivity can be actuated for up to 12 of 15 actors that can be associated with Ekip Touch via Link
                                    Bus (see Ekip Link module, page 155).
                                    Parameters
                                    The function enabling parameter, available from among the parameters that can be set for the protection,
                                    must be set for each protection for which Zone Selectivity must be activated.
                                    In this case, in addition to these parameters, Selectivity time is also activated for the setting.
                                    Otherwise, Zone Selectivity can only be set up via the Ekip Connect software.
                                           NOTE: all the following parameters and configurations are available via Ekip Connect, with
                                           Ekip Link connected and on



                            Setting Certain parameters can be configured in the Ekip Link configuration page:
                                     •  selection of selectivity type: hardware or mixed (hardware and logic)
                                     •  entry of the IP address of each actor present; entry of the address enables the configuration
                                       parameters and status indicators to be displayed in the various pages
                                     •  the function must be enabled for each actor associated with Ekip Touch via Link Bus and for which
                                       logic selectivity must be actuated (the Actor Selectivity parameter must be given value: True)
                                    selectivity masks are available in the Ekip Link advanced selectivity page for each actor present: the
                                    mask allows the protections of the actors (S, I, 2I, MCR, G, D-Forward, D-Backward, S2) that activate the
                                    selectivity input of Ekip Touch to be selected (example: actor 1, protection mask S= S2: selectivity S of Ekip
                                    Touch will be active in the presence of signals S2 of actor 1).
                                    In this configuration, if the function is enabled for S protection and is in the alarm status, the S/D-Forward
                                    hardware block signal and the logic selectivity S bit are activated on the output; depending on the block
                                    signals:
                                     •  if, on the input, the S/D-Forward hardware block signal and the logic selectivity S2 bit of actor 1 is
                                       not activated, the open command is sent in accordance with the selectivity time set for S protection
                                     •  a time equal to the trip time of S protection is waited if, on the input, the S/D-Forward hardware
                                       block signal is activated or mixed selectivity has been selected and the S2 logic selectivity bit of
                                       actor 1 is activated (and the open command is only sent if S protection is still in the alarm status
                                       once this time has elapsed)
                                           NOTES:
                                            •  the logic selectivity bits on the output and on the input are those in the data packages
                                              shared by the releases via Link Bus
                                            •  the S/D-Forward (G/D-Backward) hardware output is only activated if the S or D-Forward
                                              (G or D-Backward) protections are in the alarm status, and the S/DForward (G/D-Backward)
                                              hardware input only acts as a block for the S and D-Forward (G and D-Backward) protections,
                                              regardless of whether solely hardware or mixed selectivity has been selected
                                           IMPORTANT: if solely hardware selectivity has been selected, the logic selectivity bits
                                           are ignored on the input, but are still activated on the output

                                    Selectivity masks
                                    Remote Programmable States A and B are also included in the selectivity masks: these 2 parameters,
                                    which are available in the Ekip Link configuration page, enable the event (or combination of several events)
                                    and reference actor that activates the selectivity input to be selected.
                                    2 further states are available,  C and  D, but they cannot be configured for Zone Selectivity. All 4
                                    programmable states are used for the Programmable Logic function (see Ekip Link module on page 155).
                                           NOTE: the Programmable Logic function is independent from that of Zone Selectivity
















       79 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                  Protections | 11 - Logic selectivity
   76   77   78   79   80   81   82   83   84   85   86